<strong>and</strong> is turned into a superheated vapor. The air passing over the<br />

evaporator coil will become colder than during normal operation.<br />

However, as this same air passes over the Humidi-MiZer<br />

reheat coil, it will be warmed to meet the supply air set point<br />

temperature requirement. See Fig. 16.<br />

Temperature Compensated <strong>Start</strong> — This logic is<br />

used when the unit is in the unoccupied state. The control will<br />

calculate early <strong>Start</strong> Bias time based on Space Temperature<br />

deviation from the occupied cooling <strong>and</strong> heating set points.<br />

This will allow the control to start the unit so that the space is at<br />

conditioned levels when the occupied period starts. This is<br />

required for ASHRAE 90.1 compliance. A space sensor is required<br />

for non-linkage applications.<br />

Airflow<br />

EVAPORATOR<br />

Evaporator Discharge Temperature<br />

In Subcool or Reheat Mode, compressor staging<br />

<strong>and</strong> increased subcooling drives evaporator<br />

discharge temperature down to meet higher latent<br />

loads<br />

82<br />

SETTING UP THE SYSTEM — The settings for temperature<br />

compensated start can be found in the local display under<br />

ConfigurationUNIT.<br />

ITEM EXPANSION RANGE UNITS CCN POINT<br />

TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL<br />

TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT<br />

TCST-Cool Factor (TCS.C) — This is the factor for the start<br />

time bias equation for cooling.<br />

TCST-Heat Factor (TCS.H) — This is the factor for the start<br />

time bias equation for heating.<br />

NOTE: Temperature compensated start is disabled when these<br />

factors are set to 0.<br />

HUMIDI-MIZER ADAPTIVE<br />

DEHUMIDIFICATION<br />

SYSTEM COIL<br />

CCT SAT<br />

D.C.SP COOL<br />

Fig. 15 — Humidi-MiZer ® System Control<br />

Fig. 16 — Humidi-MiZer System Diagram<br />

Supply Air Temperature Control<br />

Innovative algorithm to control supply air temperature<br />

modulates flow bypass to meet desired supply air setpoint -<br />

no overcooling or overheating of the space.<br />

Subcooling Mode: Meet Cooling Mode Supply Air Setpoint<br />

Reheat Mode: Meet Return Air Offset or Reheat Setpoint (configurable)<br />

RAT-D.V.RA or<br />

D.V.HT<br />

CIRCUIT B CIRCUIT A