APPENDIX B — CCN TABLES (cont)<br />
STATUS DISPLAY TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
UOUTPUTS<br />
FANS<br />
Supply Fan Relay On/Off SFAN<br />
Supply Fan Comm<strong>and</strong>ed % 0-100 % SFAN_VFD<br />
Supply Fan Request Yes/No SFANFORC forcible<br />
Exhaust Fan Comm<strong>and</strong>ed % 0-100 % EFAN_VFD<br />
Power Exhaust Relay 1 On/Off PE1<br />
Power Exhaust Relay 2 On/Off PE2<br />
Condenser Fan Output 1 On/Off CONDFAN1<br />
Condenser Fan Output 2 On/Off CONDFAN2<br />
Condenser Fan Output 3 On/Off CONDFAN3<br />
Condenser Fan Output 4 On/Off CONDFAN4<br />
COOLING<br />
Compressor A1 Relay On/Off CMPA1<br />
Compressor A2 Relay On/Off CMPA2<br />
Compressor A3 Relay On/Off CMPA3<br />
Compressor B1 Relay On/Off CMPB1<br />
Compressor B2 Relay On/Off CMPB2<br />
Compressor B3 Relay On/Off CMPB3<br />
Compressor A1 Capacity % CMPA1CAP<br />
Minimum Load Valve Relay On/Off MLV<br />
Humidimizer 3-Way Valve On/Off HUM3WVAL<br />
Condenser EXV Position % COND_EXV<br />
Bypass EXV Position % BYP_EXV<br />
HEATING<br />
Heat Relay 1 On/Off HS1<br />
Heat Relay 2 On/Off HS2<br />
Relay 3 W1 Gas Valve 2 On/Off HS3<br />
Relay 4 W2 Gas Valve 2 On/Off HS4<br />
Relay 5 W1 Gas Valve 3 On/Off HS5<br />
Relay 6 W2 Gas Valve 3 On/Off HS6<br />
Heat Interlock Relay On/Off HIR forcible<br />
ACTUATORS<br />
Economizer Act.Curr.Pos. 0-100 % ECONOPOS<br />
Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS<br />
Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible<br />
Economzr 2 Act.Curr.Pos. 0-100 % ECN2RPOS<br />
Econ Comm<strong>and</strong> Position 0-100 % ECN2CPOS<br />
Humidifer Act.Curr.Pos. 0-100 % HUMDRPOS<br />
Humidifier Comm<strong>and</strong> Pos. 0-100 % HUMDCPOS<br />
Ht.Coil Act.Current Pos. 0-100 % HTCLRPOS<br />
Ht.Coil Comm<strong>and</strong> Position 0-100 % HTCLCPOS<br />
BP 1 Actuator Curr.Pos. 0-100 % BP1_RPOS<br />
BP 1 Comm<strong>and</strong> Position 0-100 % BP1_CPOS<br />
BP 2 Actuator Curr.Pos. 0-100 % BP2_RPOS<br />
BP 2 Comm<strong>and</strong> Position 0-100 % BP2_CPOS<br />
GENERAL OUTPUTS<br />
Humidifier Relay On/Off HUMIDRLY<br />
Remote Alarm / Aux Relay On/Off ALRM forcible<br />
VFD_DATA<br />
VFD1 Status Word 1 VFD1STAT<br />
VFD1 Actual Speed % % VFD1_SPD<br />
VFD1 Actual Motor RPM VFD1RPM<br />
VFD1 Actual Motor Freq VFD1FREQ<br />
VFD1 Actual Motor Amps amps VFD1AMPS<br />
VFD1 Actual Motor Torque % VFD1TORQ<br />
VFD1 Actual Motor Power VFD1PWR<br />
VFD1 DC Bus Voltage volts VFD1VDC<br />
VFD1 Output Voltage volts VFD1VOUT<br />
VFD1 Transistor Temp (C) VFD1TEMP<br />
VFD1 Cumulative Run Time hours VFD1RUNT<br />
VFD1 Cumulative kWh VFD1KWH<br />
VFD1 Last Fault Code VFD1LFC<br />
VFD1 DI1 State Open/Close VFD1_DI1<br />
VFD1 DI2 State Open/Close VFD1_DI2<br />
VFD1 DI3 State Open/Close VFD1_DI3<br />
VFD1 DI4 State Open/Close VFD1_DI4<br />
VFD1 DI5 State Open/Close VFD1_DI5<br />
VFD1 DI6 State Open/Close VFD1_DI6<br />
VFD1 AI1 (% of range) % VFD1_AI1<br />
VFD1 AI2 (% of range) % VFD1_AI2<br />
VFD2 Status Word 1 VFD2STAT<br />
VFD2 Actual Speed % VFD2_SPD<br />
VFD2 Actual Motor RPM VFD2RPM<br />
VFD2 Actual Motor Freq VFD2FREQ<br />
VFD2 Actual Motor Amps amps VFD2AMPS<br />
VFD2 Actual Motor Torque % VFD2TORQ<br />
VFD2 Actual Motor Power VFD2PWR<br />
VFD2 DC Bus Voltage volts VFD2VDC<br />
VFD2 Output Voltage volts VFD2VOUT<br />
VFD2 Transistor Temp (C) VFD2TEMP<br />
VFD2 Cumulative Run Time hours VFD2RUNT<br />
VFD2 Cumulative kWh VFD2KWH<br />
VFD2 Last Fault Code VFD2LFC<br />
VFD2 DI1 State Open/Close VFD2_DI1<br />
VFD2 DI2 State Open/Close VFD2_DI2<br />
VFD2 DI3 State Open/Close VFD2_DI3<br />
VFD2 DI4 State Open/Close VFD2_DI4<br />
VFD2 DI5 State Open/Close VFD2_DI5<br />
VFD2 DI6 State Open/Close VFD2_DI6<br />
VFD2 AI1 (% of range) % VFD2_AI1<br />
VFD2 AI2 (% of range) % VFD2_AI2<br />
179