APPENDIX B — CCN TABLES (cont)<br />
SERVICE-CONFIG TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT<br />
ALLM<br />
SPT lo alert limit/occ -10-245 dF SPLO 60<br />
SPT hi alert limit/occ -10-245 dF SPHO 85<br />
SPT lo alert limit/unocc -10-245 dF SPLU 45<br />
SPT hi alert limit/unocc -10-245 dF SPHU 100<br />
EDT lo alert limit/occ -40-245 dF SALO 40<br />
EDT hi alert limit/occ -40-245 dF SAHO 100<br />
EDT lo alert limit/unocc -40-245 dF SALU 40<br />
EDT hi alert limit/unocc -40-245 dF SAHU 100<br />
RAT lo alert limit/occ -40-245 dF RALO 60<br />
RAT hi alert limit/occ -40-245 dF RAHO 90<br />
RAT lo alert limit/unocc -40-245 dF RALU 40<br />
RAT hi alert limit/unocc -40-245 dF RAHU 100<br />
OAT lo alert limit -40-245 dF OATL -40<br />
OAT hi alert limit -40-245 dF OATH 150<br />
RARH low alert limit 0-100 % RRHL 0<br />
RARH high alert limit 0-100 % RRHH 100<br />
OARH low alert limit 0-100 % ORHL 0<br />
OARH high alert limit 0-100 % ORHH 100<br />
SP low alert limit 0-5 "H2O SPL 0<br />
SP high alert limit 0-5 "H2O SPH 2<br />
BP lo alert limit -0.25-0.25 "H2O BPL -0.25<br />
BP high alert limit -0.25-0.25 "H2O BPH 0.25<br />
IAQ high alert limit 0-5000 IAQH 1200<br />
BP__<br />
Building Press. Config 0-5 BLDG_CFG 0<br />
Building Pressure Sensor Enable/Disable BPSENS Disable<br />
Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O BP_RANGE 0.25<br />
Building Pressure Setp. -0.25 - 0.25 "H2O BPSP 0.05<br />
BP Setpoint Offset 0 - 0.5 ^"H2O BPSO 0.05<br />
Power Exhaust On Setp.1 0 - 100 % PES1 25<br />
Power Exhaust On Setp.2 0 - 100 % PES2 75<br />
VFD/Act. Fire Speed/Pos. 0 - 100 % BLDGPFSO 100<br />
VFD/Act. Min. Speed/Pos. 0 - 100 % BLDGPMIN 10<br />
VFD Maximum Speed 0 - 100 % BLDGPMAX 100<br />
BP 1 Actuator Max Pos. 85 - 100 % BP1SETMX 100<br />
BP 2 Actuator Max Pos. 85 - 100 % BP2SETMX 100<br />
BP Hi Cap VFD Clamp Val. 5 - 25 % BLDGCLMP 10<br />
Fan Track Learn Enable Yes/No DCFM_CFG NO<br />
Fan Track Learn Rate 5-60 min DCFMRATE 15<br />
Fan Track Initial DCFM -20000 - 20000 CFM DCFMSTRT 2000<br />
Fan Track Max Clamp 0 - 20000 CFM DCFM_MAX 4000<br />
Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000<br />
Fan Track Internl EEPROM -20000 - 20000 CFM DCFM_OFF 0<br />
Fan Track Internal RAM -20000 - 20000 CFM DCFM_RAM 0<br />
Fan Track Reset Internal Yes/No DCFMRSET No<br />
Supply Air CFM Config 1 - 2 (multi-text strings) SCFM_CFG 1<br />
Bldg.Pres.PID Run Rate 5 - 120 sec BPIDRATE 10<br />
Bldg.Press. Prop. Gain 0 - 5 BLDGP_PG 1<br />
Bldg.Press. Integ. Gain 0 - 2 BLDGP_IG 1<br />
Bldg.Press. Deriv. Gain 0 - 5 BLDGP_DG 0.5<br />
BP 1 Serial Number 1 0 - 9999 BP_1_SN1 0<br />
BP 1 Serial Number 2 0 - 6 BP_1_SN2 0<br />
BP 1 Serial Number 3 0 - 9999 BP_1_SN3 0<br />
BP 1 Serial Number 4 0 - 254 BP_1_SN4 0<br />
BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35<br />
BP 2 Serial Number 1 0 - 9999 BP_2_SN1 0<br />
BP 2 Serial Number 2 0 - 6 BP_2_SN2 0<br />
BP 2 Serial Number 3 0 - 9999 BP_2_SN3 0<br />
BP 2 Serial Number 4 0 - 254 BP_2_SN4 0<br />
BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35<br />