the economizer modulates when attempting to follow an<br />

economizer cooling set point. Typically, they will not need<br />

adjustment. In fact, it is strongly advised not to adjust these<br />

configuration items from their default settings without first<br />

consulting a service engineering representative.<br />

In addition, the economizer cooling algorithm is designed to<br />

automatically slow down the economizer actuator’s rate of<br />

travel as outside air temperature decreases.<br />

ECONOMIZER DIAGNOSTIC HELP — Because there are<br />

so many conditions which might disable the economizer from<br />

being able to provide free cooling, the control has a display<br />

table to identify these potentially disabling sources. The user<br />

can check ACTV, the “Economizer Active” flag. If this flag is<br />

set to Yes there is no reason to check DISA (Economizer<br />

Disabling Conditions). If the flag is set to No, this means that at<br />

least one or more of the flags under the group DISA are set<br />

to Yes <strong>and</strong> the user can discover what is preventing the economizer<br />

from performing free cooling by checking the table.<br />

The economizer’s reported <strong>and</strong> comm<strong>and</strong>ed positions<br />

are also viewable, as well as outside air temperature, relative<br />

humidity, enthalpy <strong>and</strong> dew point temperature.<br />

The following information can be found under the Local<br />

Display Mode Run StatusECON. See Table 55.<br />

Economizer Control Point Determination Logic — Once the<br />

economizer is allowed to provide free cooling, the economizer<br />

must determine exactly what set point it should try to maintain.<br />

The set point the economizer attempts to maintain when “free<br />

cooling” is located at Run StatusVIEWEC.C.P. This is<br />

the economizer control point.<br />

The control selects set points differently, based on the<br />

control type of the unit. This control type can be found at<br />

ConfigurationUNITC.TYP. There are 6 types of control.<br />

C.TYP = 1 VAV-RAT<br />

C.TYP = 2 VAV-SPT<br />

C.TYP = 3 TSTAT Multi-Staging<br />

C.TYP = 4 SPT Multi-Staging<br />

If the economizer is not allowed to do free cooling, then<br />

EC.C.P = 0.<br />

If the economizer is allowed to do free cooling <strong>and</strong> the<br />

Unoccupied Free Cooling Mode is ON, then EC.C.P =<br />

SetpointsSASP + InputsRSETSA.S.R.<br />

71<br />

If the economizer is allowed to do free cooling <strong>and</strong> the<br />

Dehumidification mode is ON, then EC.C.P = the Cooling<br />

Control Point (Run StatusVIEWCL.C.P).<br />

NOTE: To check the current cooling stage go to Run Status<br />

CoolCUR.S.<br />

If the C.TYP is either 1,2,3 or 4, <strong>and</strong> the unit is in a cool<br />

mode, then EC.C.P = the Cooling Control Point (Run Status<br />

VIEWCL.C.P).<br />

Building Pressure Control — This control sequence<br />

provides control of the building pressure through the modulating<br />

flow rate functions of one of the modulating power exhaust<br />

options or through management of the return fan option. This<br />

function also provides control of the constant volume 2-stage<br />

power exhaust option. See below for available power exhaust<br />

options for each unit model.<br />

LEGEND<br />

X — Available as Factory Option<br />

S.O. — Available as Special Order<br />

NA — Not Available on this Unit<br />

VFD — Variable Frequency Drive<br />

* Sizes 075-100 only.<br />

† Factory-installed option only.<br />

Table 55 — Economizer Run Status Table<br />

UNIT<br />

CONSTANT MODULATING<br />

HIGH<br />

S.O. CAPACITY RETURN/<br />

VOLUME POWER<br />

2-STAGE EXHAUST<br />

VFD* POWER EXHAUST†<br />

EXHAUST†<br />

48/50P2,P4 X X S.O. X* X*<br />

48/50P3,P5 NA X S.O. X* X*<br />

BUILDING PRESSURE CONFIGURATION — The building<br />

pressure configurations are found at the local display under<br />

ConfigurationBP. See Table 56.<br />

Building Pressure Config (BP.CF) — This configuration selects<br />

the type of building pressure control.<br />

• BP.CF = 0, No building pressure control<br />

• BP.CF = 1, constant volume two-stage exhaust based on<br />

economizer position<br />

• BP.CF = 2, Modulating building pressure control based<br />

on building pressure sensor<br />

• BP.CF = 3, VFD controlling two exhaust fan motors<br />

• BP.CF = 4, VFD control of one of the two exhaust fan<br />

motors (sizes 075-100 with high-capacity exhaust option)<br />

• BP.CF = 5, used on sizes 075-100 with return/exhaust<br />

fan option<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS<br />

EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS<br />

ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible<br />

ACTV Economizer Active ? YES/NO ECACTIVE<br />

DISA ECON DISABLING CONDITIONS<br />

UNV.1 Econ Act. Unavailable? YES/NO ECONUNAV<br />

UNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV<br />

ENTH Enth. Switch Read High ? YES/NO ENTH<br />

DBC DBC - OAT Lockout? YES/NO DBC_STAT<br />

DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT<br />

DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT<br />

OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT<br />

DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT<br />

EDT EDT Sensor Bad? YES/NO EDT_STAT<br />

OAT OAT Sensor Bad ? YES/NO OAT_STAT<br />

FORC Economizer Forced ? YES/NO ECONFORC<br />

SFON Supply Fan Not On 30s ? YES/NO SFONSTAT<br />

CLOF Cool Mode Not In Effect? YES/NO COOL_OFF<br />

OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD<br />

HELD Econ Recovery Hold Off? YES/NO ECONHELD<br />

DH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL<br />

O.AIR OUTSIDE AIR INFORMATION<br />

OAT Outside Air Temperature dF OAT forcible<br />

OA.RH Outside Air Rel. Humidity % OARH forcible<br />

OA.E Outside Air Enthalpy OAE<br />

OA.D.T Outside Air Dewpoint Temp dF OADEWTMP