2.10 ELECTRICAL WORK<br />

Provide electrical motor driven equipment specified complete with motors,<br />

motor starters, <strong>and</strong> controls as specified herein <strong>and</strong> in Section 26 20 00<br />

INTERIOR DISTRIBUTION SYSTEM. Provide internal wiring for components of<br />

packaged equipment as an integral part of the equipment. Provide high<br />

efficiency type, single-phase, fractional-horsepower alternating-current<br />

motors, including motors that are part of a system, corresponding to the<br />

applications in accordance with NEMA MG 11. In addition to the requirements<br />

of Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM, provide polyphase,<br />

squirrel-cage medium induction motors with continuous ratings, including<br />

motors that are part of a system, that meet the efficiency ratings for<br />

premium efficiency motors in accordance with NEMA MG 1. Provide motors in<br />

accordance with NEMA MG 1 <strong>and</strong> of sufficient size to drive the load at the<br />

specified capacity without exceeding the nameplate rating of the motor.<br />

Motors shall be rated for continuous duty with the enclosure specified.<br />

Motor duty requirements shall allow for maximum frequency start-stop<br />

operation <strong>and</strong> minimum encountered interval between start <strong>and</strong> stop. Motor<br />

torque shall be capable of accelerating the connected load within 20 seconds<br />

with 80 percent of the rated voltage maintained at motor terminals during<br />

one starting period. Motor bearings shall be fitted with grease supply<br />

fittings <strong>and</strong> grease relief to outside of the enclosure.<br />

Controllers <strong>and</strong> contactors shall have auxiliary contacts for use with the<br />

controls provided. Manual or automatic control <strong>and</strong> protective or signal<br />

devices required for the operation specified <strong>and</strong> any control wiring required<br />

for controls <strong>and</strong> devices specified, but not shown, shall be provided. For<br />

packaged equipment, the manufacturer shall provide controllers, including<br />

the required monitors <strong>and</strong> timed restart.<br />

Power wiring <strong>and</strong> conduit for field installed equipment shall be provided<br />

under <strong>and</strong> conform to the requirements of Section 26 20 00 INTERIOR<br />

DISTRIBUTION SYSTEM.<br />

2.11 MISCELLANEOUS PIPING ITEMS<br />

2.11.1 Escutcheon Plates<br />

Provide one piece or split hinge metal plates for piping entering floors,<br />

walls, <strong>and</strong> ceilings in exposed spaces. Provide chromium-plated on copper<br />

alloy plates or polished stainless steel finish in finished spaces. Provide<br />

paint finish on plates in unfinished spaces.<br />

2.11.2 Pipe Sleeves<br />

Provide where piping passes entirely through walls, ceilings, roofs, <strong>and</strong><br />

floors. Sleeves are not required where drain, waste, <strong>and</strong> vent (DWV) piping<br />

passes through concrete floor slabs located on grade, except where<br />

penetrating a membrane waterproof floor.<br />

2.11.2.1 Sleeves in Masonry <strong>and</strong> Concrete<br />

Provide steel pipe sleeves or schedule 40 PVC plastic pipe sleeves. Sleeves<br />

are not required where drain, waste, <strong>and</strong> vent (DWV) piping passes through<br />

concrete floor slabs located on grade. Core drilling of masonry <strong>and</strong><br />

Section 22 00 00 Page 27