an overall aluminum-polyester or tinned-copper cable-shield tape, overall 20<br />

AWG tinned-copper cable drain wire, <strong>and</strong> overall cable insulation.<br />

2.5.5 Transformers<br />

Transformers shall be UL 5085-3 approved. Transformers shall be sized so<br />

that the connected load is no greater than 80% of the transformer rated<br />

capacity.<br />

2.6 AUTOMATIC CONTROL VALVES<br />

Valves shall have stainless-steel stems <strong>and</strong> stuffing boxes with extended<br />

necks to clear the piping insulation. Valve bodies shall meet ASME B16.34<br />

or ASME B16.15 pressure <strong>and</strong> temperature class ratings based on the design<br />

operating temperature <strong>and</strong> 150% of the system design operating pressure.<br />

Unless otherwise specified or shown, valve leakage shall meet FCI 70-2 Class<br />

IV leakage rating (0.01% of valve Kv). Unless otherwise specified or shown,<br />

valves shall have globe-style bodies. Unless otherwise specified:<br />

a. Bodies for valves 1.5 inches <strong>and</strong> smaller shall be brass or bronze, with<br />

threaded or union ends.<br />

b. Bodies for 2 inch valves shall have threaded ends.<br />

c. Bodies for valves 2 to 3 inches shall be of brass, bronze or iron.<br />

d. Bodies for valves 2.5 inches <strong>and</strong> larger shall be provided with flangedend<br />

connections.<br />

e. For modulating applications, valve Kv (Cv) shall be within 100 to 125%<br />

of the Kv (Cv) shown.<br />

f. For two position applications (where the two positions are full open<br />

<strong>and</strong> full closed) the Kv (Cv) shall be the largest available for the<br />

valve size.<br />

g. Valve <strong>and</strong> actuator combination shall be normally open or normally<br />

closed as shown.<br />

2.6.1 Ball Valves<br />

Balls shall be stainless steel or nickel plated brass. Valves shall have<br />

blow-out proof stems. In steam <strong>and</strong> high temperature hot water applications,<br />

the valve-to-actuator linkage shall provide a thermal break.<br />

2.6.2 Butterfly Valves<br />

Butterfly valves shall be threaded lug type suitable for dead-end service<br />

<strong>and</strong> modulation to the fully-closed position, with carbon-steel bodies <strong>and</strong><br />

non-corrosive discs, stainless steel shafts supported by bearings, <strong>and</strong> EPDM<br />

seats suitable for temperatures from -20 to plus 250 degrees F. The rated<br />

Kv (Cv) for butterfly valves shall be the value Kv (Cv) at 70% (60 degrees)<br />

open position. Valve leakage shall meet FCI 70-2 Class VI leakage rating.<br />

2.6.3 Two-Way Valves<br />

Section 23 09 23 Page 15