2.7.3.2 Mechanical Rooms <strong>and</strong> Other Utility Space Ventilation Dampers<br />

Utility space ventilation dampers shall be as shown. Unless otherwise<br />

shown, dampers shall be AMCA 500-D class 4 <strong>and</strong> shall not leak in excess of<br />

80 cfm per square foot at 4 inches water gauge static pressure when closed.<br />

Dampers shall be rated at not less than 1500 ft/min air velocity.<br />

2.8 SENSORS AND INSTRUMENTATION<br />

Unless otherwise specified, sensors <strong>and</strong> instrumentation shall incorporate an<br />

integral transmitter or be provided with a transmitter co-located with the<br />

sensor. Sensors <strong>and</strong> instrumentation, including their transmitters, shall<br />

meet the specified accuracy <strong>and</strong> drift requirements at the input of the<br />

connected DDC Hardware's analog-to-digital conversion. Sensors <strong>and</strong><br />

instrumentation, including their transmitters, shall meet or exceed the<br />

specified range.<br />

2.8.1 Transmitters<br />

The transmitter shall match the characteristics of the sensor. Transmitters<br />

providing analog values shall produce a linear 4-20 mAdc, 0-10 Vdc or SNVT<br />

output corresponding to the required operating range <strong>and</strong> shall have zero <strong>and</strong><br />

span adjustment. Transmitters providing binary values shall have dry<br />

contacts or SNVT output. Transmitters with SNVT output are Application<br />

Specific Controllers (ASCs) <strong>and</strong> shall meet all ASC requirements. (note: ASCs<br />

are specified in paragraph DIRECT DIGITAL CONTROL (DDC) HARDWARE)<br />

2.8.2 Temperature Sensors<br />

2.8.2.1 Sensor Ranges <strong>and</strong> Accuracy<br />

Temperature sensors may be provided without transmitters. Temperature<br />

sensors, including transmitter if used, shall have minimum operating ranges,<br />

minimum accuracy <strong>and</strong> maximum drift as specified below for the application:<br />

a. Conditioned Space Temperature<br />

(1) Operating Range: 50 to 86 degrees F.<br />

(2) Accuracy: +/- 1 degree F over the operating range.<br />

(3) Drift: Maximum 1 degree F per year.<br />

b. Unconditioned Space Temperature<br />

(1) Operating Range: 20 to 150 degrees F.<br />

(2) Accuracy: +/- 1 degree F over the range of 30 to 131 degrees F<br />

<strong>and</strong> +/- 4 degrees F over the rest of the operating range.<br />

(3) Drift: Maximum 1 degree F per year.<br />

c. Duct Temperature<br />

(1) Operating Range: 40 to 140 degrees F.<br />

Section 23 09 23 Page 17