Factory precut or premolded insulation segments shall be used under the<br />

fitting covers for elbows. Insulation segments shall be the same insulation<br />

as the pipe insulation including same density, thickness, <strong>and</strong> thermal<br />

conductivity. The covers shall be secured by PVC vapor retarder tape,<br />

adhesive, seal welding or with tacks made for securing PVC covers. Seams in<br />

the cover, <strong>and</strong> tacks <strong>and</strong> laps to adjoining pipe insulation jacket, shall be<br />

sealed with vapor retarder tape to ensure that the assembly has a continuous<br />

vapor seal.<br />

3.2.3 Aboveground Hot Pipelines<br />

3.2.3.1 General Requirements<br />

All hot pipe lines above 60 degrees F, except those piping listed in<br />

subparagraph Pipe Insulation in PART 3 as to be omitted, shall be insulated<br />

in accordance with Table 2. This includes but is not limited to the<br />

following:<br />

a. Domestic hot water supply & re-circulating system.<br />

a . Hot water heating.<br />

Insulation shall be covered, in accordance with manufacturer's<br />

recommendations, with a factory applied Type I jacket or field applied<br />

aluminum where required or seal welded PVC.<br />

3.2.3.2 Insulation for Fittings <strong>and</strong> Accessories<br />

a. General. Pipe insulation shall be tightly butted to the insulation<br />

of the fittings <strong>and</strong> accessories. The butted joints <strong>and</strong> ends shall be<br />

sealed with joint sealant. Insulation shall be marked showing the<br />

location of unions, strainers, check valves <strong>and</strong> other components that<br />

would otherwise be hidden from view by the insulation.<br />

b. Precut or Preformed. Precut or preformed insulation shall be placed<br />

around all fittings <strong>and</strong> accessories. Insulation shall be the same<br />

insulation as the pipe insulation, including same density, thickness,<br />

<strong>and</strong> thermal conductivity.<br />

c. Rigid Preformed. Where precut/preformed is unavailable, rigid<br />

preformed pipe insulation sections may be segmented into the shape<br />

required. Insulation of the same thickness <strong>and</strong> conductivity as the<br />

adjoining pipe insulation shall be used. If nesting size insulation is<br />

used, the insulation shall be overlapped 2 inches or one pipe diameter.<br />

Elbows insulated using segments shall conform to MICA Tables 12.20<br />

"Mitered Insulation Elbow".<br />

Section 23 07 00 Page 22