Ratio <strong>and</strong> verify tap settings of instrumentation, potential, <strong>and</strong> current<br />

transformers.<br />

Perform dielectric tests on insulating oil in oil circuit breakers before<br />

the breakers are energized. Test oil in accordance with ASTM D 877, <strong>and</strong><br />

provide breakdown voltage that is not less than 25,000 volts. Provide<br />

manufacturer certification that the oil contains no PCB's, <strong>and</strong> affix a<br />

label to that effect on each breaker tank <strong>and</strong> on each oil drum containing<br />

the insulating oil.<br />

Field adjust reduced-voltage starting devices to obtain optimum operating<br />

conditions. Provide test meters <strong>and</strong> instrument transformers that conform<br />

to ANSI C12.1 <strong>and</strong> IEEE C57.13.<br />

Do not energize control <strong>and</strong> protective devices until recorded test data has<br />

been approved. Provide final test reports with a cover letter/sheet<br />

clearly marked with the System name, Date, <strong>and</strong> the words "Final Test<br />

Reports - Forward to the Systems Engineer/Condition Monitoring<br />

Office/Predictive Testing Group for inclusion in the Maintenance Database."<br />

-- End of Section --<br />

SECTION 26 05 71.00 40 Page 19