1.3 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for Contractor Quality Control<br />

approval. The following shall be submitted in accordance with Section<br />

01 33 00 SUBMITTAL PROCEDURES:<br />

SD-02 Shop Drawings<br />

Panelboards; G<br />

Cable trays; G<br />

<strong>Inc</strong>lude wiring diagrams <strong>and</strong> installation details of equipment<br />

indicating proposed location, layout <strong>and</strong> arrangement, control<br />

panels, accessories, piping, ductwork, <strong>and</strong> other items that must<br />

be shown to ensure a coordinated installation. Wiring diagrams<br />

shall identify circuit terminals <strong>and</strong> indicate the internal wiring<br />

for each item of equipment <strong>and</strong> the interconnection between each<br />

item of equipment. Drawings shall indicate adequate clearance for<br />

operation, maintenance, <strong>and</strong> replacement of operating equipment<br />

devices.<br />

Wireways; G<br />

Marking strips drawings; G<br />

SD-03 Product Data<br />

Receptacles; G<br />

Circuit breakers; G<br />

Switches; G<br />

Transformers; G<br />

Enclosed circuit breakers; G<br />

Motor controllers; G<br />

Combination motor controllers; G<br />

Manual motor starters; G<br />

Metering; G<br />

CATV outlets; G<br />

Surge protective devices; G<br />

SECTION 26 20 00 Page 5