3.2.3 Local Display Panel (LDP)<br />

Local Display Panels shall be installed in each mechanical room containing<br />

an air h<strong>and</strong>ler <strong>and</strong> shall provide SNVT inputs for display <strong>and</strong> outputs for<br />

adjusting SNVT values as shown on the Points Schedule.<br />

3.2.4 Gateways<br />

Gateways may be used for communication with non-CEA-709.1B control hardware<br />

subject to all of the following limitations:<br />

a. Each gateway shall communicate with <strong>and</strong> perform protocol translation<br />

for non-CEA-709.1B control hardware controlling one <strong>and</strong> only one<br />

package unit.<br />

b. Non-CEA-709.1B control hardware shall not be used for controlling<br />

built-up units.<br />

c. Non-CEA-709.1B control hardware shall not perform system scheduling<br />

functions.<br />

3.2.5 Network Interface Jack<br />

A st<strong>and</strong>ard network interface jack shall be provided for each node on the<br />

control network. For terminal unit controllers with hardwired thermostats<br />

this network interface jack shall be located at the thermostat or within 10<br />

ft of the controller. Locating the interface jack near the controller is<br />

preferred. For all other nodes the network interface jack shall be located<br />

within 10 ft of the node. If the network interface jack is other than a 1/8<br />

inch phone jack, the Contractor shall provide an interface cable with a<br />

st<strong>and</strong>ard 1/8 inch phone jack on one end <strong>and</strong> a connector suitable for mating<br />

with installed network interface jack on the other. No more than one type<br />

of interface cable shall be required to access all network interface jacks.<br />

Contractor shall furnish one interface cable(s).<br />

3.2.6 Room Instrument Mounting<br />

Room instruments, including but not limited to wall mounted thermostats <strong>and</strong><br />

sensors located in occupied spaces shall be mounted 60 inches above the<br />

floor unless otherwise shown. Unless otherwise shown on the Thermostat<br />

Schedule:<br />

a. Thermostats for Fan Coil Units shall be unit mounted.<br />

b. All other Thermostats shall be wall mounted.<br />

3.2.7 Indication Devices Installed in Piping <strong>and</strong> Liquid Systems<br />

Gauges in piping systems subject to pulsation shall have snubbers. Gauges<br />

for steam service shall have pigtail fittings with cock. Thermometers <strong>and</strong><br />

temperature sensing elements installed in liquid systems shall be installed<br />

in thermowells.<br />

3.2.8 Temperature Limit Switch<br />