Two-way modulating valves used for liquids shall have an equal-percentage<br />

characteristic. Two-way modulating valves used for steam shall have a<br />

linear characteristic.<br />

2.6.4 Three-Way Valves<br />

Three-way modulating valves shall provide equal percentage flow control with<br />

constant total flow throughout full plug travel.<br />

2.6.5 Valves for Chilled-Water Service<br />

Valve internal trim shall be Type 316 stainless steel. Valves 4 inches <strong>and</strong><br />

larger shall be butterfly valves.<br />

2.7 DAMPERS<br />

2.7.1 Damper Assembly<br />

A single damper section shall have blades no longer than 48 inch <strong>and</strong> shall<br />

be no higher than 72 inch. Maximum damper blade width shall be 8 inch.<br />

Larger sizes shall be made from a combination of sections. Dampers shall be<br />

steel, or other materials where shown. Flat blades shall be made rigid by<br />

folding the edges. Blade-operating linkages shall be within the frame so<br />

that blade-connecting devices within the same damper section shall not be<br />

located directly in the air stream. Damper axles shall be 1/2 inch minimum,<br />

plated steel rods supported in the damper frame by stainless steel or bronze<br />

bearings. Blades mounted vertically shall be supported by thrust bearings.<br />

Pressure drop through dampers shall not exceed 0.04 inches water gauge at<br />

1,000 ft/min in the wide-open position. Frames shall not be less than 2<br />

inch in width. Dampers shall be tested in accordance with AMCA 500-D.<br />

2.7.2 Operating Linkages<br />

Operating links external to dampers, such as crank arms, connecting rods,<br />

<strong>and</strong> line shafting for transmitting motion from damper actuators to dampers,<br />

shall withst<strong>and</strong> a load equal to at least 300% of the maximum required<br />

damper-operating force. Rod lengths shall be adjustable. Links shall be<br />

brass, bronze, zinc-coated steel, or stainless steel. Working parts of<br />

joints <strong>and</strong> clevises shall be brass, bronze, or stainless steel. Adjustments<br />

of crank arms shall control the open <strong>and</strong> closed positions of dampers.<br />

2.7.3 Damper Types<br />

2.7.3.1 Flow Control Dampers<br />

Outside air, return air, relief air, exhaust, face <strong>and</strong> bypass dampers shall<br />

be provided where shown <strong>and</strong> shall be parallel-blade or opposed blade type as<br />

shown on the Damper Schedule. Blades shall have interlocking edges <strong>and</strong><br />

shall be provided with compressible seals at points of contact. The channel<br />

frames of the dampers shall be provided with jamb seals to minimize air<br />

leakage. Unless otherwise shown, dampers shall be AMCA 500-D Class 2 <strong>and</strong><br />

shall not leak in excess of 20 cfm per square foot at 4 inches water gauge<br />

static pressure when closed. Outside air damper seals shall be suitable for<br />

an operating temperature range of -40 to plus 167 degrees F. Dampers shall<br />

be rated at not less than 2000 ft/min air velocity.<br />