transportation, <strong>and</strong> on-site storage shall not exceed 12 months, thereby<br />

permitting 4 years of the ballast 5 year warranty to be in service <strong>and</strong><br />

energized. The warranty shall state that the malfunctioning ballast shall<br />

be exchanged by the manufacturer <strong>and</strong> promptly shipped to the using<br />

Government facility. The replacement ballast shall be identical to, or an<br />

improvement upon, the original design of the malfunctioning ballast.<br />

1.8 OPERATIONAL SERVICE<br />

Coordinate with manufacturer for maintenance agreement take-back program.<br />

Collect information from the manufacturer about maintenance agreement<br />

options, <strong>and</strong> submit to Contracting Officer. Services shall reclaim<br />

materials for recycling <strong>and</strong>/or reuse. Services shall not l<strong>and</strong>fill or burn<br />

reclaimed materials. Indicate procedures for compliance with regulations<br />

governing disposal of mercury. When such a service is not available, local<br />

recyclers shall be sought after to reclaim the materials.<br />

1.9 SUSTAINABLE DESIGN REQUIREMENTS<br />

1.9.1 Local/Regional Materials<br />

Use materials or products extracted, harvested, or recovered, as well as<br />

manufactured, within a 500_____ mile radius from the project site, if<br />

available from a minimum of three sources.<br />

PART 2<br />

PRODUCTS<br />

2.1 FLUORESCENT LIGHTING FIXTURES<br />

UL 1598. Fluorescent fixtures shall have electronic ballasts unless<br />

specifically indicated otherwise.<br />

2.1.1 Fluorescent Lamp Electronic Ballasts<br />

The electronic ballast shall as a minimum meet the following<br />

characteristics:<br />

a. Ballast shall comply with UL 935, NEMA ANSLG C82.11, NFPA 70, <strong>and</strong><br />

CEC Title 24 unless specified otherwise. Ballast shall be 100 percent<br />

electronic high frequency type with no magnetic core <strong>and</strong> coil<br />

components. Ballast shall provide transient immunity as recommended by<br />

IEEE C62.41.1 <strong>and</strong> IEEE C62.41.2. Ballast shall be designed for the<br />

wattage of the lamps used in the indicated application. Ballasts shall<br />

be designed to operate on the voltage system to which they are<br />

connected.<br />

b. Power factor shall be 0.95 (minimum).<br />

c. Ballast shall operate at a frequency of 20,000 Hertz (minimum).<br />

Ballast shall be compatible with <strong>and</strong> not cause interference with the<br />

operation of occupancy sensors or other infrared control systems.<br />

Provide ballasts operating at or above 40,000 Hertz where available.<br />

d. Ballast shall have light regulation of plus or minus 10 percent lumen<br />

output with a plus or minus 10 percent input voltage regulation.<br />

Ballast shall have 10 percent flicker (maximum) using any compatible<br />

lamp.<br />

e. Ballast factor shall be between 0.85 (minimum) <strong>and</strong> 1.00 (maximum).<br />

SECTION 26 51 00 Page 6