2.8.2.4 Thermowells<br />

Thermowells shall be Series 300 stainless steel with threaded brass plug <strong>and</strong><br />

chain, 2 inch lagging neck <strong>and</strong> extension type well. Inside diameter <strong>and</strong><br />

insertion length shall be as required for the application.<br />

2.8.3 Relative Humidity Sensor<br />

Relative humidity sensors shall use bulk polymer resistive or thin film<br />

capacitive type non-saturating sensing elements capable of withst<strong>and</strong>ing a<br />

saturated condition without permanently affecting calibration or sustaining<br />

damage. The sensors shall include removable protective membrane filters.<br />

Where required for exterior installation, sensors shall be capable of<br />

surviving below freezing temperatures <strong>and</strong> direct contact with moisture<br />

without affecting sensor calibration. When used indoors, the sensor shall<br />

be capable of being exposed to a condensing air stream (100% RH) with no<br />

adverse effect to the sensor's calibration or other harm to the instrument.<br />

The sensor shall be of the wall-mounted or duct-mounted type, as required by<br />

the application, <strong>and</strong> shall be provided with any required accessories.<br />

Sensors used in duct high-limit applications shall have a bulk polymer<br />

resistive sensing element. Duct-mounted sensors shall be provided with a<br />

duct probe designed to protect the sensing element from dust accumulation<br />

<strong>and</strong> mechanical damage. Relative humidity (RH) sensors shall measure<br />

relative humidity over a range of 0% to 100% with an accuracy of +/- 3%. RH<br />

sensors shall function over a temperature range of 25 to 130 degrees F <strong>and</strong><br />

shall not drift more than 2% per year.<br />

2.8.4 Differential Pressure Instrumentation<br />

2.8.4.1 Differential Pressure Sensors<br />

Differential Pressure Sensor range shall be as shown or as required for the<br />

application. Pressure sensor ranges shall not exceed the high end range<br />

shown on the Points Schedule by more than 50%. The over pressure rating<br />

shall be a minimum of 150% of the highest design pressure of either input to<br />

the sensor. The accuracy shall be +/- 2% of full scale.<br />

2.8.4.2 Differential Pressure Switch<br />

The switch shall have a user-adjustable setpoint. The setpoint shall not be<br />

in the upper or lower quarters of the range. The over pressure rating shall<br />

be a minimum of 150% of the highest design pressure of either input to the<br />

sensor. The switch shall have two sets of contacts <strong>and</strong> each contact shall<br />

have a rating greater than it's connected load. Contacts shall open or<br />

close upon rise of pressure above the setpoint or drop of pressure below the<br />

setpoint as shown.<br />

2.8.5 Flow Sensors<br />

2.8.5.1 Airflow Measurement Array (AFMA)<br />

Airflow Straightener.-AFMAs shall contain an airflow straightener if<br />

required by the AFMA manufacturer's published installation instructions.<br />

The straightener shall be contained inside a flanged sheet metal casing,<br />

with the AMFA located as specified according to the published recommendation<br />

of the AFMA manufacturer. In the absence of published documentation airflow<br />

Section 23 09 23 Page 19