integral pointer on the valve which registers the degree of valve opening.<br />

Flow through the valve shall be manually adjustable from bubble tight<br />

shutoff to full flow. Valves smaller than 2 inches shall have NPT<br />

connections. Valves 2 inches <strong>and</strong> larger shall have flanged or grooved end<br />

connections. Valve design shall allow the back seat for the stem to be<br />

replaced in the field under full line pressure.<br />

2.4.11 Water Temperature Mixing Valve<br />

Valve, ASSE 1017 for water service.<br />

2.4.12 Water Temperature Regulating Valves<br />

Provide copper alloy body, direct acting, pilot operated, for the intended<br />

service.<br />

2.4.13 Water Pressure Reducing Valve<br />

Valve, ASSE 1003 for water service, copper alloy body, automatic re-seating,<br />

with test lever.<br />

2.4.14 Pressure Relief Valve<br />

Valve shall prevent excessive pressure in the piping system when the piping<br />

system reaches its maximum heat buildup. Valve, CSA/AM Z21.22 <strong>and</strong> shall<br />

have cast iron bodies with corrosion resistant internal working parts. The<br />

discharge pipe from the relief valve shall be the size of the valve outlet<br />

unless otherwise indicated.<br />

2.4.15 Combination Pressure <strong>and</strong> Temperature Relief Valves<br />

CSA/AM Z21.22, copper alloy body, automatic re-seating, test lever, <strong>and</strong><br />

discharge capacity based on AGA temperature steam rating.<br />

2.4.16 Drain Valves<br />

Valves, MSS SP-80 gate valves. Valve shall be manually-operated, 3/4 inch<br />

pipe size <strong>and</strong> above with a threaded end connection. Provide valve with a<br />

water hose nipple adapter. Freeze-proof type valves shall be provided in<br />

installations exposed to freezing temperatures.<br />

2.4.17 Air Venting Valves<br />

Manually-operated general service type air venting valves, brass or bronze<br />

valves that are furnished with threaded plugs or caps. Automatic type air<br />

venting shall be the ball-float type with brass/bronze or brass bodies, 300<br />

series corrosion-resistant steel float, linkage <strong>and</strong> removable seat. Air<br />

venting valves on water coils shall have not less than 1/8 inch threaded<br />

end connections. Air venting valves on water mains shall have not less than<br />

3/4 inch threaded end connections. Air venting valves on all other<br />

applications shall have not less than 1/2 inch threaded end connections.<br />

2.4.18 Vacuum Relief Valves<br />

CSA/ANSI Z21.22<br />