c. The local control bus shall use Bacnet MS/TP over a TP/FT-10 network<br />

d. The local control busses shall be installed such that no node (device<br />

connected to the control network) has more than two CEA-709.1B Routers<br />

<strong>and</strong> CEA-709.3 Repeaters (in any combination) between it <strong>and</strong> the<br />

backbone, including the router connected to the backbone.<br />

e. All DDC Hardware shall connect to a local control bus.<br />

f. All DDC Hardware shall be locally powered; link power is not<br />

acceptable.<br />

PART 2<br />

PRODUCTS<br />

PART 2 of this specification covers requirements for Products (equipment).<br />

Installation requirements for these products are covered in PART 3 of this<br />

specification.<br />

2.1 EQUIPMENT<br />

2.1.1 General Requirements<br />

Units of the same type of equipment shall be products of a single<br />

manufacturer. Each major component of equipment shall have the<br />

manufacturer's name <strong>and</strong> address, <strong>and</strong> the model <strong>and</strong> serial number in a<br />

conspicuous place. Materials <strong>and</strong> equipment shall be st<strong>and</strong>ard products of a<br />

manufacturer regularly engaged in the manufacturing of these <strong>and</strong> similar<br />

products. The st<strong>and</strong>ard products shall have been in a satisfactory<br />

commercial or industrial use for two years prior to use on this project.<br />

The two year use shall include applications of equipment <strong>and</strong> materials under<br />

similar circumstances <strong>and</strong> of similar size. DDC Hardware not meeting the<br />

two-year field service requirement shall be acceptable provided it has been<br />

successfully used by Keesler AFB in a minimum of two previous projects. The<br />

equipment items shall be supported by a service organization. Items of the<br />

same type <strong>and</strong> purpose shall be identical, including equipment, assemblies,<br />

parts <strong>and</strong> components. Manufacturer's catalog data sheets documenting<br />

compliance with product specifications shall be submitted as specified for<br />

each product installed under this specification.<br />

2.1.2 Operation Environment Requirements<br />

All products shall be rated for continuous operation under the following<br />

conditions:<br />

a. Pressure: Pressure conditions normally encountered in the installed<br />

location.<br />

b. Vibration: Vibration conditions normally encountered in the installed<br />

location.<br />

c. Temperature:<br />

(1) Products installed indoors: Ambient temperatures in the range of<br />

32 to 112 degrees F <strong>and</strong> temperature conditions outside this range<br />

normally encountered at the installed location.<br />

Section 23 09 23 Page 12