shall be weatherproof. The housings of recess mounted switches <strong>and</strong> magnets<br />

shall be made of nonferrous metal or plastic.<br />

2.2.1.2 Remote Test<br />

Provide a remote test capability. The remote test shall be initiated when<br />

comm<strong>and</strong>ed by the alarm annunciation system. The remote test shall activate<br />

the sensor's switch mechanism causing an alarm signal to be transmitted to<br />

the alarm annunciation system. The remote test shall simulate the movement<br />

of the actuating magnet relative to the switch subassembly.<br />

2.2.2 Passive Infrared Motion Sensor<br />

The passive infrared motion sensor shall detect changes in the ambient<br />

level of infrared emissions caused by the movement of a st<strong>and</strong>ard intruder<br />

within the sensor's field of view. Upon detecting such changes, the sensor<br />

shall transmit an alarm signal to the alarm annunciation system. The<br />

sensor shall detect a change in temperature of no more than 2 degrees F,<br />

<strong>and</strong> shall detect a st<strong>and</strong>ard intruder traveling within the sensor's<br />

detection pattern at a speed of 0.3 to 7.5 feet per second across two<br />

adjacent segments of the field of view. Emissions monitored by the sensor<br />

shall be in the 8 to 14 micron range. The sensor shall be adjustable to<br />

obtain the coverage pattern shown. The sensor shall be equipped with a<br />

temperature compensation circuit.<br />

2.2.2.1 Test Indicator, Infrared Emissions<br />

The passive infrared motion sensor shall be equipped with an LED walk test<br />

indicator. The walk test indicator shall not be visible during normal<br />

operations. When visible, the walk test indicator shall light when the<br />

sensor detects an intruder. The sensor shall either be equipped with a<br />

manual control, located within the sensor's housing, to enable/disable the<br />

test indicator or the test indicator shall be located within the sensor<br />

such that it can only be seen when the housing is open/removed.<br />

2.2.2.2 Remote Test, Infrared Emissions<br />

Provide a remote test capability. The remote test hardware may be integral<br />

to the sensor or a separate piece of equipment. The remote test shall be<br />

initiated when comm<strong>and</strong>ed by the alarm annunciation system. The remote test<br />

shall excite the sensing element <strong>and</strong> associated electronics causing an<br />

alarm signal to be transmitted to the alarm annunciation system. The<br />

sensor stimulation generated by the remote test hardware shall simulate a<br />

st<strong>and</strong>ard intruder moving within the sensor's detection pattern.<br />

2.3 FIELD PROCESSING HARDWARE<br />

2.3.1 Alarm Annunciation Local Processor<br />

The alarm annunciation local processor shall respond to interrogations from<br />

the field device network, recognize <strong>and</strong> store alarm status inputs until<br />

they are transmitted to the central station <strong>and</strong> change outputs based on<br />

comm<strong>and</strong>s received from the central station. The local processor shall also<br />

automatically restore communication within 10 seconds after an interruption<br />

with the field device network <strong>and</strong> provide dc line supervision on each of<br />

its alarm inputs.<br />

a. Inputs. Local processor inputs shall monitor dry contacts for change<br />

of state that reflect alarm conditions. The local processor shall have<br />

SECTION 28 16 01.00 10 Page 10