A temperature limit switch (freezestat) shall be provided to sense the<br />

temperature at the location shown. A sufficient number of temperature limit<br />

switches (freezestats) shall be installed to provide complete coverage of<br />

the duct section. Manual reset limit switches shall be installed in<br />

approved, accessible locations where they can be reset easily. The<br />

temperature limit switch (freezestat) sensing element shall be installed in<br />

a serpentine pattern <strong>and</strong> in accordance with the manufacturer's installation<br />

instructions.<br />

3.2.9 Averaging Temperature Sensing Elements<br />

Sensing elements shall be installed in a serpentine pattern located as<br />

shown.<br />

3.2.10 Air Flow Measurement Arrays (AFMA))<br />

Outside Air AFMAs shall be located downstream from the Outside Air filters.<br />

Pitot Tube AFMA shall not be used if the expected velocity measurement is<br />

below 700 fpm or for outside airflow measurements.<br />

3.2.11 Duct Static Pressure Sensors<br />

The duct static pressure sensing tap shall be located at 75% to 100% of the<br />

distance between the first <strong>and</strong> last air terminal units. If the transmitter<br />

is wired in a homerun configuration to an AHU controller, the transmitter<br />

shall be located in the same enclosure as the air h<strong>and</strong>ling unit (AHU)<br />

controller(s) for the AHU serving the terminal units.<br />

3.2.12 Relative Humidity Sensors<br />

Relative humidity sensors in supply air ducts shall be installed at least 10<br />

feet downstream of humidity injection elements.<br />

3.2.13 Flowmeters<br />

The minimum straight unobstructed piping for the flowmeter installation<br />

shall be at least 10 pipe diameters upstream <strong>and</strong> at least 5 pipe diameters<br />

downstream <strong>and</strong> in accordance with the manufacturer's installation<br />

instructions.<br />

3.2.14 Dampers<br />

3.2.14.1 Damper Actuators<br />

Actuators shall not be mounted in the air stream. Multiple actuators shall<br />

not be connected to a common drive shaft. Actuators shall be installed so<br />

that their action shall seal the damper to the extent required to maintain<br />

leakage at or below the specified rate <strong>and</strong> shall move the blades smoothly.<br />

3.2.14.2 Damper Installation<br />

Dampers shall be installed straight <strong>and</strong> true, level in all planes, <strong>and</strong><br />

square in all dimensions. Dampers shall move freely without undue stress<br />

due to twisting, racking (parallelogramming), bowing, or other installation<br />

error. Blades shall close completely <strong>and</strong> leakage shall not exceed that<br />

specified at the rated static pressure. Structural support shall be used<br />

Section 23 09 23 Page 29