(1) On pipe 4 inches <strong>and</strong> larger when the temperature of the medium is<br />

60 degrees F or higher, a Type 39 saddle, welded to the pipe, may<br />

freely rest on a steel plate.<br />

(2) On pipe less than 4 inches a Type 40 shield, attached to the pipe<br />

or insulation, may freely rest on a steel plate.<br />

(3) On pipe 4 inches <strong>and</strong> larger carrying medium less that 60 degrees<br />

F a Type 40 shield, attached to the pipe or insulation, may freely<br />

rest on a steel plate.<br />

l. Pipe hangers on horizontal insulated pipe shall be the size of the<br />

outside diameter of the insulation. The insulation shall be continuous<br />

through the hanger on all pipe sizes <strong>and</strong> applications.<br />

m. Where there are high system temperatures <strong>and</strong> welding to piping is not<br />

desirable, the type 35 guide shall include a pipe cradle, welded to the<br />

guide structure <strong>and</strong> strapped securely to the pipe. The pipe shall be<br />

separated from the slide material by at least 4 inches or by an amount<br />

adequate for the insulation, whichever is greater.<br />

n. Hangers <strong>and</strong> supports for plastic pipe shall not compress, distort, cut<br />

or abrade the piping, <strong>and</strong> shall allow free movement of pipe except<br />

where otherwise required in the control of expansion/contraction.<br />

3.1.7.3 Structural Attachments<br />

Attachment to building structure concrete <strong>and</strong> masonry shall be by cast-in<br />

concrete inserts, built-in anchors, or masonry anchor devices. Inserts <strong>and</strong><br />

anchors shall be applied with a safety factor not less than 5. Supports<br />

shall not be attached to metal decking. Supports shall not be attached to<br />

the underside of concrete filled floor or concrete roof decks unless<br />

approved by the Contracting Officer. Masonry anchors for overhead<br />

applications shall be constructed of ferrous materials only.<br />

3.1.8 Welded Installation<br />

Plumbing pipe weldments shall be as indicated. Changes in direction of<br />

piping shall be made with welding fittings only; mitering or notching pipe<br />

to form elbows <strong>and</strong> tees or other similar type construction will not be<br />

permitted. Branch connection may be made with either welding tees or forged<br />

branch outlet fittings. Branch outlet fittings shall be forged, flared for<br />

improvement of flow where attached to the run, <strong>and</strong> reinforced against<br />

external strains. Beveling, alignment, heat treatment, <strong>and</strong> inspection of<br />

weld shall conform to ASME B31.1. Weld defects shall be removed <strong>and</strong> repairs<br />

made to the weld, or the weld joints shall be entirely removed <strong>and</strong> rewelded.<br />

After filler metal has been removed from its original package, it shall be<br />

protected or stored so that its characteristics or welding properties are<br />

not affected. Electrodes that have been wetted or that have lost any of<br />

their coating shall not be used.<br />

3.1.9 Pipe Cleanouts<br />

Pipe cleanouts shall be the same size as the pipe except that cleanout plugs<br />

larger than 4 inches will not be required. A cleanout installed in<br />

connection with cast-iron soil pipe shall consist of a long-sweep 1/4 bend<br />

Section 22 00 00 Page 37