3.2.8 Duct Test Holes<br />

Provide holes with closures or threaded holes with plugs in ducts <strong>and</strong><br />

plenums as indicated or where necessary for the use of pitot tube in<br />

balancing the air system. Plug insulated duct at the duct surface, patched<br />

over with insulation <strong>and</strong> then marked to indicate location of test hole if<br />

needed for future use.<br />

3.2.9 Power Transmission Components Adjustment<br />

Test V-belts <strong>and</strong> sheaves for proper alignment <strong>and</strong> tension prior to operation<br />

<strong>and</strong> after 72 hours of operation at final speed. Uniformly load belts on<br />

drive side to prevent bouncing. Make alignment of direct driven couplings<br />

to within 50 percent of manufacturer's maximum allowable range of<br />

misalignment.<br />

3.3 EQUIPMENT PADS<br />

Provide equipment pads to the dimensions shown or, if not shown, to conform<br />

to the shape of each piece of equipment served with a minimum 3-inch margin<br />

around the equipment <strong>and</strong> supports. Allow equipment bases <strong>and</strong> foundations,<br />

when constructed of concrete or grout, to cure a minimum of 28 calendar days<br />

before being loaded.<br />

3.4 CUTTING AND PATCHING<br />

Install work in such a manner <strong>and</strong> at such time that a minimum of cutting <strong>and</strong><br />

patching of the building structure is required. Make holes in exposed<br />

locations, in or through existing floors, by drilling <strong>and</strong> smooth by s<strong>and</strong>ing.<br />

Use of a jackhammer is permitted only where specifically approved. Make<br />

holes through masonry walls to accommodate sleeves with an iron pipe masonry<br />

core saw.<br />

3.5 CLEANING<br />

Thoroughly clean surfaces of piping <strong>and</strong> equipment that have become covered<br />

with dirt, plaster, or other material during h<strong>and</strong>ling <strong>and</strong> construction<br />

before such surfaces are prepared for final finish painting or are enclosed<br />

within the building structure. Before final acceptance, clean mechanical<br />

equipment, including piping, ducting, <strong>and</strong> fixtures, <strong>and</strong> free from dirt,<br />

grease, <strong>and</strong> finger marks. When the work area is in an occupied space such<br />

as office, laboratory or warehouse protect all furniture <strong>and</strong> equipment from<br />

dirt <strong>and</strong> debris. <strong>Inc</strong>orporate housekeeping for field construction work which<br />

leaves all furniture <strong>and</strong> equipment in the affected area free of construction<br />

generated dust <strong>and</strong> debris; <strong>and</strong>, all floor surfaces vacuum-swept clean.<br />

3.6 PENETRATIONS<br />

Provide sleeves <strong>and</strong> prepared openings for duct mains, branches, <strong>and</strong> other<br />

penetrating items, <strong>and</strong> install during the construction of the surface to be<br />

penetrated. Cut sleeves flush with each surface. Place sleeves for round<br />

duct 15 inches <strong>and</strong> smaller. Build framed, prepared openings for round duct<br />

larger than 15 inches <strong>and</strong> square, rectangular or oval ducts. Sleeves <strong>and</strong><br />

framed openings are also required where grilles, registers, <strong>and</strong> diffusers<br />

are installed at the openings. Provide one inch clearance between<br />

penetrating <strong>and</strong> penetrated surfaces except at grilles, registers, <strong>and</strong><br />