shall have a range suitable for the application with an upper end of the<br />

range not to exceed 150% of the design upper limit.<br />

2.9.1.1 Piping System Thermometers<br />

Piping system thermometers shall have brass, malleable iron or aluminum<br />

alloy case <strong>and</strong> frame, clear protective face, permanently stabilized glass<br />

tube with indicating-fluid column, white face, black numbers, <strong>and</strong> a 9 inch<br />

scale. Piping system thermometers shall have an accuracy of +/- 1% of scale<br />

range. Thermometers for piping systems shall have rigid stems with<br />

straight, angular, or inclined pattern. Thermometer stems shall have<br />

expansion heads as required to prevent breakage at extreme temperatures. On<br />

rigid-stem thermometers, the space between bulb <strong>and</strong> stem shall be filled<br />

with a heat-transfer medium.<br />

2.9.2 Pressure Gauges<br />

Gauges shall be suitable for field or panel mounting as required, shall have<br />

black legend on white background, <strong>and</strong> shall have a pointer traveling through<br />

a 270-degree arc. Gauge range shall be suitable for the application with an<br />

upper end of the range not to exceed 150% of the design upper limit.<br />

Accuracy shall be +/- 3% of scale range. Gauges shall meet requirements of<br />

ASME B40.100.<br />

2.9.3 Low Differential Pressure Gauges<br />

Gauges for low differential pressure measurements shall be a minimum of 3.5<br />

inch (nominal) size with two sets of pressure taps, <strong>and</strong> shall have a<br />

diaphragm-actuated pointer, white dial with black figures, <strong>and</strong> pointer zero<br />

adjustment. Gauge range shall be suitable for the application with an upper<br />

end of the range not to exceed 150% of the design upper limit. Accuracy<br />

shall be plus or minus two percent of scale range.<br />

2.10 OUTPUT DEVICES<br />

Output Devices with SNVT input are ASCs <strong>and</strong> shall meet all ASC requirements<br />

in addition to the output device requirements. (Note: ASCs are specified in<br />

paragraph DIRECT DIGITAL CONTROL (DDC) HARDWARE.)<br />

2.10.1 Actuators<br />

Actuators shall be electric (electronic) . All actuators shall be normally<br />

open (NO), normally closed (NC) or fail-in-last-position (FILP) as shown.<br />

Normally open <strong>and</strong> normally closed actuators shall be of mechanical spring<br />

return type. Electric actuators shall have an electronic cut off or other<br />

means to provide burnout protection if stalled. Actuators shall have a<br />

visible position indicator. Electric actuators shall provide position<br />

feedback to the controller as shown. Actuators shall smoothly open or close<br />

the devices to which they are applied. Pneumatic actuators shall have a<br />

full stroke response time matching the connected Electric to Pneumatic<br />

Transducer (EP). Electric actuators shall have a full stroke response time<br />

in both directions of 90 seconds or less at rated load. Electric actuators<br />

shall be of the foot-mounted type with an oil-immersed gear train or the<br />

direct-coupled type. Where multiple electric actuators operate from a<br />

common signal, the actuators shall provide an output signal identical to its<br />

input signal to the additional devices.<br />

Section 23 09 23 Page 22