3.5.1 Identification Tags<br />

Identification tags made of brass, engraved laminated plastic, or engraved<br />

anodized aluminum, indicating service <strong>and</strong> valve number shall be installed on<br />

valves, except those valves installed on supplies at plumbing fixtures. Tags<br />

shall be 1-3/8 inch minimum diameter, <strong>and</strong> marking shall be stamped or<br />

engraved. Indentations shall be black, for reading clarity. Tags shall be<br />

attached to valves with No. 12 AWG, copper wire, chrome-plated beaded chain,<br />

or plastic straps designed for that purpose.<br />

3.5.2 Pipe Color Code Marking<br />

Color code marking of piping shall be as specified in Section 09 90 00<br />

PAINTS AND COATINGS.<br />

3.5.3 Color Coding Scheme for Locating Hidden Utility Components<br />

Scheme shall be provided in buildings having suspended grid ceilings. The<br />

color coding scheme shall identify points of access for maintenance <strong>and</strong><br />

operation of operable components which are not visible from the finished<br />

space <strong>and</strong> installed in the space directly above the suspended grid ceiling.<br />

The operable components shall include valves, dampers, switches, linkages<br />

<strong>and</strong> thermostats. The color coding scheme shall consist of a color code<br />

board <strong>and</strong> colored metal disks. Each colored metal disk shall be<br />

approximately 3/8 inch in diameter <strong>and</strong> secured to removable ceiling panels<br />

with fasteners. The fasteners shall be inserted into the ceiling panels so<br />

that the fasteners will be concealed from view. The fasteners shall be<br />

manually removable without tools <strong>and</strong> shall not separate from the ceiling<br />

panels when panels are dropped from ceiling height. Installation of colored<br />

metal disks shall follow completion of the finished surface on which the<br />

disks are to be fastened. The color code board shall have the approximate<br />

dimensions of 3 foot width, 30 inches height, <strong>and</strong> 1/2 inch thickness. The<br />

board shall be made of wood fiberboard <strong>and</strong> framed under glass or 1/16 inch<br />

transparent plastic cover. Unless otherwise directed, the color code<br />

symbols shall be approximately 3/4 inch in diameter <strong>and</strong> the related<br />

lettering in 1/2 inch high capital letters. The color code board shall be<br />

mounted <strong>and</strong> located in the mechanical or equipment room. The color code<br />

system shall be as indicated below:<br />

Color System Item Location<br />

3.6 ESCUTCHEONS<br />

Escutcheons shall be provided at finished surfaces where bare or insulated<br />

piping, exposed to view, passes through floors, walls, or ceilings, except<br />

in boiler, utility, or equipment rooms. Escutcheons shall be fastened<br />

securely to pipe or pipe covering <strong>and</strong> shall be satin-finish, corrosionresisting<br />

steel, polished chromium-plated zinc alloy, or polished chromiumplated<br />

copper alloy. Escutcheons shall be either one-piece or splitpattern,<br />

held in place by internal spring tension or setscrew.<br />

3.7 PAINTING<br />

Section 22 00 00 Page 43