a. Mineral Fiber: ASTM C 547, Types I, II or III, supply the<br />

insulation with manufacturer's recommended factory-applied jacket.<br />

b. Calcium Silicate: ASTM C 533, Type I indoor only, or outdoors<br />

above 250 degrees F pipe temperature. Supply insulation with the<br />

manufacturer's recommended factory-applied jacket/vapor barrier.<br />

c. Cellular Glass: ASTM C 552, Type II <strong>and</strong> Type III. Supply the<br />

insulation with manufacturer's recommended factory-applied jacket.<br />

d. Flexible Elastomeric Cellular Insulation: ASTM C 534/C 534M, Grade<br />

1, Type I or II to 200 degrees F service.<br />

e. Phenolic Insulation: ASTM C 1126 Type III to 250 degrees F service<br />

shall comply with ASTM C 795. Supply the insulation with<br />

manufacturer's recommended factory-applied jacket/vapor barrier.<br />

f. Perlite Insulation: ASTM C 610<br />

g. Polyisocyanurate Insulation: ASTM C 591, Type 1, to 300 degrees F<br />

service. Supply the insulation with manufacturer's recommended factory<br />

applied jacket/vapor barrier.<br />

h. Flexible Polyolefin Cellular Insulation: ASTM C 1427, Grade 1 Type<br />

I or II to 200 degrees F.<br />

2.3.3 Below-ground Pipeline Insulation<br />

For below-ground pipeline insulation the following requirements shall be<br />

met.<br />

2.3.3.1 Cellular Glass<br />

ASTM C 552, type II.<br />

2.3.3.2 Polyisocyanurate<br />

ASTM C 591, Type 1, to 300 degrees F.<br />

2.4 DUCT INSULATION SYSTEMS<br />

2.4.1 Duct Insulation<br />

Provide factory-applied cellular glass polyisocyanurate or phenolic foam<br />

insulation with insulation manufacturer's st<strong>and</strong>ard reinforced fire-retardant<br />

vapor barrier , with identification of installed thermal resistance (R)<br />

value <strong>and</strong> out-of-package R value.<br />

2.4.1.1 Rigid Insulation<br />

Rigid mineral fiber in accordance with ASTM C 612, Class 2 (maximum surface<br />

temperature 400 degrees F), 3 pcf average, 1-1/2 inch thick, Type IA, IB,<br />

II, III, <strong>and</strong> IV. Alternately, minimum thickness may be calculated in<br />

accordance with ASHRAE 90.1 - IP.<br />

Section 23 07 00 Page 11