. The hardware shall perform the control sequences as specified <strong>and</strong> shown<br />

to provide control of the equipment as specified <strong>and</strong> shown.<br />

c. Control sequence logic shall reside in DDC hardware in the building.<br />

The building control network shall not be dependent upon connection to<br />

a Utility Monitoring <strong>and</strong> Control System (UMCS) for performance of<br />

control sequences in this specification. The hardware shall, to the<br />

greatest extent practical, perform the sequences without reliance on<br />

the building network.<br />

d. The hardware shall be installed such that individual control equipment<br />

can be replaced by similar control equipment from other equipment<br />

manufacturers with no loss of system functionality.<br />

e. All necessary documentation, configuration information, configuration<br />

tools, programs, drivers, <strong>and</strong> other software shall be licensed to <strong>and</strong><br />

otherwise remain with the Government such that the Government or their<br />

agents are able to perform repair, replacement, upgrades, <strong>and</strong><br />

expansions of the system without subsequent or future dependence on the<br />

Contractor.<br />

f. The Contractor shall provide sufficient documentation <strong>and</strong> data,<br />

including rights to documentation <strong>and</strong> data, such that the Government or<br />

their agents can execute work to perform repair, replacement, upgrades,<br />

<strong>and</strong> expansions of the system without subsequent or future dependence on<br />

the Contractor.<br />

g. Hardware shall be installed <strong>and</strong> configured such that the Government or<br />

their agents are able to perform repair, replacement, <strong>and</strong> upgrades of<br />

individual hardware without further interaction with the Contractor.<br />

h. Control hardware shall be installed <strong>and</strong> configured to provide all input<br />

<strong>and</strong> output St<strong>and</strong>ard Network Variables (SNVTs) as shown <strong>and</strong> as needed to<br />

meet the requirements of this specification.<br />

i. All DDC devices installed under this specification shall communicate<br />

via Bacnet MS/TP. The control system shall be installed such that a<br />

SNVT output from any node on the network can be bound to any other node<br />

in the domain.<br />

1.4.2 Verification of Dimensions<br />

After becoming familiar with all details of the work, the Contractor shall<br />

verify all dimensions in the field, <strong>and</strong> shall advise the Contracting Officer<br />

of any discrepancy before performing any work.<br />

1.4.3 Drawings<br />

The Government will not indicate all offsets, fittings, <strong>and</strong> accessories that<br />

may be required on the drawings. The Contractor shall carefully investigate<br />

the mechanical, electrical, <strong>and</strong> finish conditions that could affect the work<br />

to be performed, shall arrange such work accordingly, <strong>and</strong> shall provide all<br />

work necessary to meet such conditions.<br />

1.5 PROJECT SEQUENCING<br />

Section 23 09 23 Page 7