PH<br />

Nitrite or Molybdate<br />

Conductivity<br />

ppm (mg/L)<br />

micromho/cm<br />

3.5.2 Hot Water Boiler Water Quality Testing<br />

3.5.2.1 Low <strong>and</strong> Medium Temperature Systems (monthly)<br />

Monthly testing shall be completed <strong>and</strong> recorded for the following<br />

parameters.<br />

PH<br />

Nitrite or Molybdate<br />

ppm (mg/L)<br />

3.5.3 Quality Assurance Testing<br />

Conduct quality assurance testing periodically by an independent water<br />

treatment lab/consultant to verify to managers that the mechanical <strong>and</strong> water<br />

treatment systems are being maintained properly. Provide the Quality<br />

Assurance evaluation reports to the government COR.<br />

3.5.3.1 Chilled Water Quality Assurance Testing (quarterly)<br />

Quarterly, the following tests shall be performed on chilled water.<br />

PH<br />

Nitrite or Molybdate<br />

Conductivity<br />

Iron (total, as Fe(2)O(3))<br />

Written evaluation summary<br />

ppm (mg/L)<br />

micromho/cm<br />

ppm (mg/L)<br />

3.5.3.2 Hot Water Boiler Water Quality Assurance Testing<br />

a. Quarterly testing of Low <strong>and</strong> Medium Temperature Systems shall be<br />

completed <strong>and</strong> recorded for the following parameters.<br />

PH<br />

Nitrite or Molybdate<br />

Iron (total, as Fe(2)O(3))<br />

Written evaluation summary<br />

ppm (mg/L)<br />

ppm (mg/L)<br />

b. The hot water boiler water shall be analyzed once a month for a<br />

period of 1 year by an independent consultant. The analysis shall<br />

include the following information recorded in accordance with ASTM D<br />

596.<br />

PH<br />

Sulfite (Na2SO3)<br />

Hardness(as CaCO3)<br />

Iron (total, as Fe(2)O(3))<br />

Written evaluation summary<br />

ppm (mg/L)<br />

ppm (mg/L)<br />

ppm (mg/L)<br />

3.5.4 Corrosion Testers<br />