2.5.4.1 Operating Controls<br />

Chiller shall be provided with the following adjustable operating controls<br />

as a minimum.<br />

a. Leaving chilled water temperature control<br />

b. Adjustable timer or automated controls to prevent a compressor from<br />

short cycling<br />

c. Automatic lead/lag controls (adjustable) for multi-compressor units<br />

d. Load limiting<br />

e. System capacity control to adjust the unit capacity in accordance<br />

with the system load <strong>and</strong> the programmable setpoints. Controls<br />

shall automatically re-cycle the chiller on power interruption.<br />

f. Startup <strong>and</strong> head pressure controls to allow system operation at all<br />

ambient temperatures down to 0 degrees F<br />

2.5.4.2 Monitoring Capabilities<br />

During normal operations, the control system shall be capable of monitoring<br />

<strong>and</strong> displaying the following operating parameters. Access <strong>and</strong> operation of<br />

display shall not require opening or removing any panels or doors.<br />

a. Entering <strong>and</strong> leaving chilled water temperatures<br />

b. Self diagnostic<br />

c. Operation status<br />

d. Operating hours<br />

e. Number of starts<br />

f. Compressor status (on or off)<br />

g. Refrigerant discharge <strong>and</strong> suction pressures<br />

h. Oil pressure<br />

2.5.4.3 Programmable Setpoints<br />

The control system shall be capable of being reprogrammed directly at the<br />

unit. [No parameters shall be capable of being changed without first<br />

entering a security access code.] The programmable setpoints shall include<br />

the following as a minimum.<br />

a. Leaving Chilled Water Temperature<br />

Section 23 64 10 Page 9