PART 3<br />

EXECUTION<br />

3.1 INSTALLATION<br />

Electrical installations shall conform to IEEE C2, NFPA 70, <strong>and</strong> to the<br />

requirements specified herein.<br />

3.1.1 Lamps<br />

Lamps of the type, wattage, <strong>and</strong> voltage rating indicated shall be delivered<br />

to the project in the original cartons <strong>and</strong> installed just prior to project<br />

completion. Lamps installed <strong>and</strong> used for working light during construction<br />

shall be replaced prior to turnover to the Government if more than 15<br />

percent of their rated life has been used. Lamps shall be tested for<br />

proper operation prior to turn-over <strong>and</strong> shall be replaced if necessary with<br />

new lamps from the original manufacturer. Provide 10 percent spare lamps<br />

of each type from the original manufacturer.<br />

3.1.2 Lighting Fixtures<br />

Set lighting fixtures plumb, square, <strong>and</strong> level with ceiling <strong>and</strong> walls, in<br />

alignment with adjacent lighting fixtures, <strong>and</strong> secure in accordance with<br />

manufacturers' directions <strong>and</strong> approved drawings. Installation shall meet<br />

requirements of NFPA 70. Mounting heights specified or indicated shall be<br />

to the bottom of fixture for ceiling-mounted fixtures <strong>and</strong> to center of<br />

fixture for wall-mounted fixtures. Obtain approval of the exact mounting<br />

for lighting fixtures on the job before commencing installation <strong>and</strong>, where<br />

applicable, after coordinating with the type, style, <strong>and</strong> pattern of the<br />

ceiling being installed. Recessed <strong>and</strong> semi-recessed fixtures shall be<br />

independently supported from the building structure by a minimum of four<br />

wires or straps or rods per fixture <strong>and</strong> located near each corner of each<br />

fixture. Ceiling grid clips are not allowed as an alternative to<br />

independently supported light fixtures. Round fixtures or fixtures smaller<br />

in size than the ceiling grid shall be independently supported from the<br />

building structure by a minimum of four wires or straps or rods per fixture<br />

spaced approximately equidistant around the fixture. Do not support<br />

fixtures by ceiling acoustical panels. Where fixtures of sizes less than<br />

the ceiling grid are indicated to be centered in the acoustical panel,<br />

support such fixtures independently <strong>and</strong> provide at least two 3/4 inch metal<br />

channels spanning, <strong>and</strong> secured to, the ceiling tees for centering <strong>and</strong><br />

aligning the fixture. Provide wires or straps or rods for lighting fixture<br />

support in this section. Lighting fixtures installed in suspended ceilings<br />

shall also comply with the requirements of Section 09 51 00 ACOUSTICAL<br />

CEILINGS.<br />

3.1.3 Suspended Fixtures<br />

Suspended fixtures shall be provided with 45 degree swivel hangers so that<br />

they hang plumb <strong>and</strong> shall be located with no obstructions within the 45<br />

degree range in all directions. The stem, canopy <strong>and</strong> fixture shall be<br />

capable of 45 degree swing. Pendants, rods, or chains 4 feet or longer<br />

excluding fixture shall be braced to prevent swaying using three cables at<br />

120 degree separation. Suspended fixtures in continuous rows shall have<br />

internal wireway systems for end to end wiring <strong>and</strong> shall be properly<br />

aligned to provide a straight <strong>and</strong> continuous row without bends, gaps, light<br />

leaks or filler pieces. Aligning splines shall be used on extruded<br />

aluminum fixtures to assure hairline joints. Steel fixtures shall be<br />

supported to prevent "oil-canning" effects. Fixture finishes shall be free<br />

of scratches, nicks, dents, <strong>and</strong> warps, <strong>and</strong> shall match the color <strong>and</strong> gloss<br />

SECTION 26 51 00 Page 12