1.3.7 System Reaction<br />

All alarms shall be annunciated on the displays within 1 second of their<br />

occurring at a local processor.<br />

1.3.8 System Capacity<br />

The system shall monitor <strong>and</strong> control the number of inputs <strong>and</strong> outputs shown<br />

<strong>and</strong> shall include an expansion capability of a minimum of 25 percent.<br />

1.4 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for Contractor Quality Control<br />

approval. Submit the following in accordance with Section 01 33 00<br />

SUBMITTAL PROCEDURES:<br />

SD-03 Product Data<br />

Intrusion Detection System; G<br />

Manufacturer's Instructions; G<br />

Testing; G<br />

Experience<br />

SD-06 Test Reports<br />

Performance Verification Test<br />

SD-07 Certificates<br />

Materials <strong>and</strong> Equipment<br />

1.5 QUALITY ASSURANCE<br />

Submit written proof that the following experience requirements are being<br />

met.<br />

1.5.1 Hardware Manufacturer<br />

All system components shall be produced by manufacturers who have been<br />

regularly engaged in the production of intrusion detection system<br />

components of the types to be installed for at least 3 years.<br />

1.5.2 Software Manufacturer<br />

All system <strong>and</strong> application software shall be produced by manufacturers who<br />

have been regularly engaged in the production of intrusion detection system<br />

<strong>and</strong> application software of similar type <strong>and</strong> complexity as the specified<br />

system for at least 2 years.<br />

1.5.3 System Installer<br />

The system shall be installed by a Contractor who has been regularly<br />

engaged in the installation of intrusion detection systems of similar type<br />

<strong>and</strong> complexity as the specified system for at least 2 years.<br />

SECTION 28 16 01.00 10 Page 4