embossed or greater than 8 ply (minimum 2.9 mils adhesive), heavy duty,<br />

white or natural). Application procedures shall match the<br />

manufacturer's written instructions.<br />

h. At termination points, other than building entrances, the mastic<br />

<strong>and</strong> cloth or tape shall cover the ends of insulation <strong>and</strong> extend 2<br />

inches along the bare pipe.<br />

3.3 DUCT INSULATION SYSTEMS INSTALLATION<br />

Except for oven hood exhaust duct insulation, corner angles shall be<br />

installed on external corners of insulation on ductwork in exposed finished<br />

spaces before covering with jacket. Air conditioned spaces shall be<br />

defined as those spaces directly supplied with cooled conditioned air (or<br />

provided with a cooling device such as a fan-coil unit) <strong>and</strong> heated<br />

conditioned air (or provided with a heating device such as a unit heater,<br />

radiator or convector).<br />

3.3.1 Duct Insulation Thickness<br />

Duct insulation thickness shall be in accordance with Table 4.<br />

Table 4 - Minimum Duct Insulation (inches)<br />

Cold Air Ducts 2.0<br />

Relief Ducts 1.5<br />

Fresh Air Intake Ducts 1.5<br />

Warm Air Ducts 2.0<br />

Relief Ducts 1.5<br />

Fresh Air Intake Ducts 1.5<br />

3.3.2 Insulation <strong>and</strong> Vapor Retarder/Vapor Barrier for Cold Air Duct<br />

Insulation <strong>and</strong> vapor retarder/vapor barrier shall be provided for the<br />

following cold air ducts <strong>and</strong> associated equipment.<br />

a. Supply ducts.<br />

b. Return air ducts.<br />

c. Relief ducts.<br />

d. Flexible run-outs (field-insulated).<br />

e. Plenums.<br />

f. Duct-mounted coil casings.<br />

g. Coil headers <strong>and</strong> return bends.<br />

h. Coil casings.<br />

i. Fresh air intake ducts.<br />

Section 23 07 00 Page 25