15.01.2015 Views

Specifications - Lord and Son Construction, Inc.

Specifications - Lord and Son Construction, Inc.

Specifications - Lord and Son Construction, Inc.

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

for multi-section dampers. Acceptable methods include but are not limited<br />

to U-channel, angle iron, corner angles <strong>and</strong> bolts, bent galvanized steel<br />

stiffeners, sleeve attachments, braces, <strong>and</strong> building structure. Where<br />

multi-section dampers are installed in ducts or sleeves, they shall not sag<br />

due to lack of support. Jackshafts shall not be used to link more than<br />

three damper sections. Blade to blade linkages shall not be used. Outside<br />

<strong>and</strong> return air dampers shall be installed such that their blades direct<br />

their respective air streams towards each other to provide for maximum<br />

mixing of air streams.<br />

3.2.15 Valves<br />

3.2.15.1 Ball Valves<br />

Two-position (open/closed) ball valves may only be used on chilled water,<br />

condenser water, hot water, or steam applications. Modulating ball valves<br />

may only be used for chilled water <strong>and</strong> condenser water applications<br />

(modulating ball valves shall not be used on steam or hot water<br />

applications). In modulating applications a characterizing equal-percentage<br />

disc shall be used.<br />

3.2.15.2 Butterfly Valves<br />

In two-way control applications, valve travel shall be limited to 70% (60<br />

degrees) open position.<br />

3.2.16 Local Gauges for Actuators<br />

Pneumatic actuators shall have an accessible <strong>and</strong> visible pressure gauge<br />

installed in the tubing lines at the actuator as shown.<br />

3.2.17 Wire <strong>and</strong> Cable<br />

Wire <strong>and</strong> Cable shall be installed without splices between control devices <strong>and</strong><br />

in accordance with NFPA 70 <strong>and</strong> NFPA 90A. Instrumentation grounding shall be<br />

installed per the device manufacturer's instructions <strong>and</strong> as necessary to<br />

prevent ground loops, noise, <strong>and</strong> surges from adversely affecting operation of<br />

the system. Ground rods installed by the Contractor shall be tested as<br />

specified in IEEE Std 142. Cables <strong>and</strong> conductor wires shall be tagged at<br />

both ends, with the identifier shown on the shop drawings. Electrical work<br />

shall be as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM <strong>and</strong> as<br />

shown. Wiring external to enclosures shall be run in raceways<br />

3.2.18 Copper Tubing<br />

Copper tubing shall be hard-drawn in exposed areas <strong>and</strong> either hard-drawn or<br />

annealed in concealed areas. Only tool-made bends shall be used. Fittings<br />

for copper tubing shall be brass or copper solder joint type except at<br />

connections to apparatus, where fittings shall be brass compression type.<br />

3.2.19 Plastic Tubing<br />

Plastic tubing shall be run within covered raceways or conduit except when<br />

otherwise specified. Plastic tubing shall not be used for applications<br />

where the tubing could be subjected to a temperature exceeding 130 degrees<br />

F. Fittings for plastic tubing shall be for instrument service <strong>and</strong> shall be<br />

Section 23 09 23 Page 30

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!