shall be made without prior approval of the Government. Any modifications<br />

made to the system shall be incorporated into the Operations <strong>and</strong> Maintenance<br />

Instructions, <strong>and</strong> other documentation affected.<br />

1.10 SURGE PROTECTION<br />

1.10.1 Power-Line Surge Protection<br />

Equipment connected to ac circuits shall be protected against or withst<strong>and</strong><br />

power-line surges. Equipment protection shall meet the requirements of IEEE<br />

C62.41.1, IEEE C62.41.2. Fuses shall not be used for surge protection.<br />

1.10.2 Surge Protection for Transmitter <strong>and</strong> Control Wiring<br />

DDC hardware shall be protected against or withst<strong>and</strong> surges induced on<br />

control <strong>and</strong> transmitter wiring installed outdoors <strong>and</strong> as shown. The<br />

equipment protection shall be protected against the following two waveforms:<br />

a. A waveform with a 10-microsecond rise time, a 1,000-microsecond decay<br />

time <strong>and</strong> a peak current of 60 amps.<br />

b. A waveform with an 8-microsecond rise time, a 20-microsecond decay time<br />

<strong>and</strong> a peak current of 500 amperes.<br />

1.11 INPUT MEASUREMENT ACCURACY<br />

Sensors, transmitters <strong>and</strong> DDC Hardware shall be selected, installed <strong>and</strong><br />

configured such that the maximum error of the measured value at the SNVT<br />

output of the DDC hardware is less than 150% of the maximum allowable error<br />

specified for the sensor or instrumentation.<br />

1.12 BUILDING CONTROL NETWORK<br />

The building control network shall consist of a backbone <strong>and</strong> one or more<br />

local control busses as specified. The DDC system shall be an extension of<br />

the existing Metasys ADX server. The application specific controllers used<br />

for this project shall perfectly match the application specific controllers<br />

used in the building 0308 building renovation.<br />

1.12.1 Backbone Media<br />

The backbone shall be a TP/FT-10 network in accordance with CEA-709.3 or an<br />

IP network according to the following criteria:<br />

b. The backbone shall be a TP/FT-10 network otherwise.<br />

1.12.2 Control Network Requirements<br />

The control network shall meet the following requirements:<br />

a. The backbone shall have no control devices connected to it.<br />

b. The backbone shall be installed such that a router at the Building Point<br />

of Connection (BPOC) location as shown may be connected to the<br />

backbone.<br />

Section 23 09 23 Page 11