Occupancy Output shall be determined by the default schedule <strong>and</strong> the<br />

Space Occupancy Inputs. Otherwise, the output shall be determined as<br />

follows:<br />

(1) If the Override Occupancy Input is not OC_NUL, the Air H<strong>and</strong>ler<br />

Occupancy Output shall determined as follows:<br />

(a) The output shall be Occupied when the Override OccupancyInput<br />

is OC_OCCUPIED.<br />

(b) The output shall be Unoccupied when the Override<br />

OccupancyInput is OC_UNOCCUPIED.<br />

(c) If the system Sequence Of Operation specifies Warm-Up-Cool-<br />

Down mode, the output shall be Warm-Up-Cool-Down when the Override<br />

Occupancy Input is OC_STANDBY.<br />

(2) If the Override Occupancy Input is OC_NUL <strong>and</strong> the Schedule<br />

Occupancy input is OC_OCCUPIED, the Air H<strong>and</strong>ler <strong>and</strong> St<strong>and</strong>-Alone<br />

Terminal Unit Occupancy Output shall be OC_OCCUPIED.<br />

(3) If the Override Occupancy Input is OC_NUL, the Schedule Occupancy<br />

input is not OC_OCCUPIED, <strong>and</strong> less than required number of Space<br />

Occupancy Inputs (as shown on the Occupancy Schedule Drawing) are<br />

OC_OCCUPIED (or the hardware BI is Unoccupied), the Air H<strong>and</strong>ler<br />

Occupancy Output shall be determined by the Scheduled Occupancy<br />

Input<br />

(a) The output shall be Occupied when the Scheduled Occupancy<br />

Input is OC_OCCUPIED.<br />

(b) The output shall be Unoccupied when the Scheduled Occupancy<br />

Input is OC_UNOCCUPIED.<br />

(c) If the system Sequence Of Operation specifies Warm-Up-Cool-<br />

Down mode the output shall be Warm-Up-Cool-Down when the Scheduled<br />

Occupancy Input is OC_STANDBY.<br />

(4) If the Override Occupancy Input is OC_NUL <strong>and</strong> at least the<br />

required number (as shown on the Occupancy Schedule Drawing) of<br />

Space Occupancy Inputs are OC_OCCUPIED (or the hardware BI is<br />

Occupied), the Air H<strong>and</strong>ler Occupancy Output shall be Occupied.<br />

3.4.2.4 Air H<strong>and</strong>ler System Scheduling<br />

The AHU Occupancy Output SNVT shall be bound from the System Scheduler to<br />

the DDC Hardware that executes the Occupancy Mode Determination part of the<br />

Air H<strong>and</strong>ler Sequence of Operation.<br />

For Air H<strong>and</strong>lers using occupancy sensors, the occupancy sensor output SNVT<br />

(of type SNVT_Occupancy) shall be bound to a Space Occupancy Input of the<br />

System Scheduler.<br />

Section 23 09 23 Page 35