Fan Coil Unit Number FC -<br />

Identify similar services with different temperatures or pressures. Where<br />

pressures could exceed 125 pounds per square inch, gage, include the maximum<br />

system pressure in the label. Label <strong>and</strong> arrow piping in accordance with the<br />

following:<br />

a. Each point of entry <strong>and</strong> exit of pipe passing through walls.<br />

b. Each change in direction, i.e., elbows, tees.<br />

c. In congested or hidden areas <strong>and</strong> at all access panels at each point<br />

required to clarify service or indicated hazard.<br />

d. In long straight runs, locate labels at distances within eyesight of<br />

each other not to exceed 75 feet. All labels shall be visible <strong>and</strong><br />

legible from the primary service <strong>and</strong> operating area.<br />

For Bare or Insulated Pipes<br />

for Outside Diameters of<br />

Lettering<br />

1/2 thru 1-3/8 inch 1/2 inch<br />

1-1/2 thru 2-3/8 inch 3/4 inch<br />

2-1/2 inch <strong>and</strong> larger 1-1/4 inch<br />

1.2.3 Color Coding<br />

Color coding of all piping systems shall be in accordance with ASME A13.1 .<br />

1.3 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for information only. When<br />

used, a designation following the "G" designation identifies the office that<br />

will review the submittal for the Government. Submit the following in<br />

accordance with Section 01 33 00 SUBMITTAL PROCEDURES:<br />

SD-03 Product Data<br />

Metallic Flexible Duct<br />

Insulated Nonmetallic Flexible Duct Runouts<br />

Duct Connectors<br />

Duct Access Doors; G<br />

Manual Balancing Dampers; G<br />

Diffusers<br />

Registers <strong>and</strong> Grilles<br />

Louvers<br />

Section 23 00 00 Page 4