horizontal installations. The only air in the system shall be the permanent<br />

sealed-in air cushion contained within the expansion tank.<br />

2.8 AIR SEPARATOR TANKS<br />

External air separation tank shall have an internal design constructed of<br />

stainless steel <strong>and</strong> suitable for creating the required vortex <strong>and</strong> subsequent<br />

air separation. Tank shall be steel, constructed for, <strong>and</strong> tested to<br />

pressure-temperature rating of 125 psi at 150 degrees F. Tank shall have<br />

tangential inlets <strong>and</strong> outlets connections, threaded for 2 inches <strong>and</strong> smaller<br />

<strong>and</strong> flanged for sizes 2-1/2 inches <strong>and</strong> larger. Air released from a tank<br />

shall be to the atmosphere . Tank shall be provided with a blow-down<br />

connection.<br />

Design to separate air from water <strong>and</strong> to direct released air to automatic<br />

air vent. Unit shall be of one piece cast-iron construction with internal<br />

baffles <strong>and</strong> two air chambers at top of unit; one air chamber shall have<br />

outlet to expansion tank <strong>and</strong> other air chamber shall be provided with<br />

automatic air release device. Tank shall be steel, constructed for, <strong>and</strong><br />

tested to a ANSI Class 125 pressure-temperature rating.<br />

2.9 WATER TREATMENT SYSTEMS<br />

When water treatment is specified, the use of chemical-treatment products<br />

containing equivalent chromium (CPR) is prohibited.<br />

2.9.1 Water Analysis<br />

Conditions of make-up water to be supplied to the condenser <strong>and</strong> chilled<br />

water systems were reported in accordance with ASTM D 596 <strong>and</strong> are as<br />

follows:<br />

Date of Sample<br />

Temperature degrees F.<br />

Silica (Sino 2)<br />

pp (mg/1)<br />

Insoluble<br />

pp (mg/1)<br />

Iron <strong>and</strong> Aluminum Oxides<br />

pp (mg/1)<br />

Calcium (Ca)<br />

pp (mg/1)<br />

Magnesium (Mg)<br />

pp (mg/1)<br />

Sodium <strong>and</strong> Potassium (Nan <strong>and</strong> AK)<br />

pp (mg/1)<br />

Carbonate (HO 3)<br />

pp (mg/1)<br />

Sulfate (SO 4)<br />

pp (mg/1)<br />

Chloride (JCL)<br />

pp (mg/1)<br />

Nitrate (NO 3)<br />

pp (mg/1)<br />

Turbidity<br />

unit<br />

pH<br />

Residual Chlorine<br />

pp (mg/1)<br />

Total Alkalinity<br />

PM (me/1)<br />

Non-Carbonate Hardness<br />

PM (me/1)<br />

Total Hardness<br />

PM (me/1)<br />

Dissolved Solids<br />

pp (mg/1)<br />

Fluorine<br />

pp (mg/1)<br />

Conductivity<br />

McMahon/cm<br />

Section 23 64 26 Page 19