Guide Specification<br />

Optical Fiber Wavelength Maximum attenuation Minimum information transmission<br />

Cable Type (nm) (dB/km)<br />

capacity for overfilled launch (MHz/km)<br />

62.5/125 µm 850 3.5 200<br />

multimode 1300 1.5 500<br />

Singlemode ISP 8 1310 1.0 N/A*<br />

cable<br />

1550 1.0 N/A*<br />

Singlemode 8.0 1310 0.5 N/A*<br />

OSP cable 1550 0.5 N/A*<br />

*Note – The information capacity of the fiber, as measured by the fiber manufacturer, can be used b<br />

the contractor to demonstrate compliance with this requirement.<br />

N. General: Cables <strong>and</strong> components that fail performance tests shall be replaced <strong>and</strong> retested until<br />

they meet the required performance st<strong>and</strong>ards.<br />

O. Fiber Optic Cable:<br />

1. Record cable length from either length markings on cable or through OTDR test.<br />

2. After installing connectors perform OTDR on all fibers to evaluate connector loss <strong>and</strong><br />

validate connector.<br />

a. <strong>Los</strong>s shall not exceed manufacturer's listed maximum loss for connector type<br />

installed.<br />

b. Connector shall be replaced at Contractors expense if it fails test.<br />

3.9 HORIZONTAL UNSHIELDED CABLE TESTING<br />

A. Test all new UTP cables.<br />

B. Testing shall conform to ANSI/TIA/EIA TSB-67 Transmission Performance Specifications for<br />

Field Testing of Unshielded Twisted-Pair Cabling Systems <strong>and</strong> ANSI/TIA/EIA-568-C.2,<br />

Propagation Delay <strong>and</strong> Delay Skew Specification for 100 Ohm 4-Pair Cable.<br />

C. Testing shall be accomplished using a UL certified Level III tester.<br />

D. Notify Owner of any cable failing the prescribed certification testing.<br />

E. The Contractor shall provide Category 6, 100 MHz channel test results on all pairs of cable,<br />

including but not limited to cable length, wire map, NEXT, Power Sum NEXT, ACR, Power<br />

Sum ACR, ELFEXT, Power Sum ELFEXT, Return <strong>Los</strong>s, Propagation Delay <strong>and</strong> Delay Skew.<br />

Results shall be provided in an electronic format.<br />

3.10 BACKBONE CABLE TESTING<br />

A. Testing shall be according to device manufacturer’s specification. Testing for cable integrity<br />

after installation shall be performed to include as a minimum, DC resistance, opens or shorts.<br />

BASIC TELECOMMUNICATIONS REQUIREMENTS<br />

27 05 00 - 21<br />

Communication Systems