Guide Specification<br />

1. Utilize bare stable springs without restraints.<br />

2. Provide spring with diameter not less than 80% of loaded operating height of spring.<br />

3. <strong>Design</strong> ends of spring so that they remain parallel during <strong>and</strong> after springs are loaded to<br />

their minimum specified deflections.<br />

4. Provide springs with 50% travel from operating deflection before reaching solid height.<br />

5. Provide spring mounts with 1/4 inch thick waffled neoprene acoustical pad bonded to<br />

underside of base plate.<br />

H. Provide resiliently mounted equipment bases raised to operating height with a minimum of 2<br />

inch of clearance at bottom of base prior to installing equipment.<br />

1. Temporarily support bases on 2-inch thick (minimum) spacer blocks.<br />

2. Adjust mountings to transfer load from spacer blocks to mountings; remove spacer blocks<br />

after equipment installation, but immediately prior to operation.<br />

I. Concrete inertia blocks with adequate reinforcing steel will be provided under General<br />

<strong>Construction</strong> Work.<br />

J. Neoprene-In-Shear Isolation Rails: Furnish for horizontal pumps, air compressors, <strong>and</strong><br />

vacuum pumps when supplied with fractional horsepower motors.<br />

1. Provide top structural iron channel rails with tapped holes to accept machinery<br />

foundation bolts supported by properly loaded <strong>and</strong> located double deflection neoprene-inshear<br />

mountings, equal to Type DNR - M.I.I.<br />

2. Provide mountings with 3/8 inch minimum static deflection <strong>and</strong> bolt holes for anchoring<br />

onto foundation equal to Type DNR - M.I.I.<br />

K. Neoprene-In-Shear Supported Concrete Inertia Bases: Provide for horizontal pumps, jockey<br />

pumps, air compressors, <strong>and</strong> vacuum pumps when supplied with one horsepower to three<br />

horsepower motors.<br />

L. Provide a minimum 6-inch thick concrete inertia block supported by double deflection<br />

neoprene-in-shear mountings, equal to Type ND - M.I.I., with form as noted for foundations.<br />

Bolt <strong>and</strong> grout equipment to concrete base. Provide minimum static deflection of 1 inch.<br />

M. Spring-Supported, Factory-Fabricated Inertia Bases: Provide for horizontal pumps (except<br />

fire pumps), bottom-supported vertical booster pumps, jockey pumps, rotary air compressors<br />

<strong>and</strong> vacuum pumps with five horsepower <strong>and</strong> larger motors.<br />

1. Provide concrete inertia block with factory-fabricated steel structural perimeter frame, set<br />

on roofing paper, with equipment anchor bolt templates <strong>and</strong> mounting brackets supplied<br />

by vibration control manufacturer.<br />

2. Provide <strong>and</strong> locate under brackets, spring supports with a minimum static deflection of 1<br />

inch <strong>and</strong> with leveling device to raise entire isolation base 2 inch above foundation.<br />

3. Provide minimum thickness required for concrete inertia bases as follows:<br />

a. Motor Size 5 hp to 15 hp: 6 inch.<br />

b. Motor Size 20 hp to 50 hp: 8 inch.<br />

c. Motor Size 60 hp to 100 hp: 10 inch.<br />

d. Motor Size Over 100 hp: 12 inch.<br />

HANGERS AND SUPPORTS FOR PLUMBING AND EQUIPMENT<br />

22 05 29 - 14 Plumbing Systems