Guide Specification<br />

2. Provide three dual input telephone interface stations.<br />

X. Loudspeakers shall be the type <strong>and</strong> number depicted in the contract drawings <strong>and</strong> as required by<br />

the Contract Documents.<br />

Y. Amplification shall:<br />

1. Be provided as shown in the Contract Drawings.<br />

2. Provide full b<strong>and</strong>width signals to those loudspeakers that have a single, full range audio<br />

input.<br />

3. Provide crossovers <strong>and</strong> a high <strong>and</strong> low frequency signal to those loudspeakers which are<br />

bi-amplified.<br />

4. Be capable of supplying 4 Ohm, 8 Ohm, 16 Ohm <strong>and</strong> 70 Volt output without the use of a<br />

transformer.<br />

5. Be provided with adequate cooling for the amplifiers, as recommended by the amplifier’s<br />

manufacturer.<br />

Z. Connection to the emergency announcement system:<br />

1. Emergency messaging shall be automatically initiated whenever the system is notified of<br />

a general alarm condition in the new Terminal.<br />

PAGING SYSTEMS<br />

27 51 13 - 14<br />

a. Whenever a local alarm condition is detected by the fire alarm system, the fire<br />

alarm system will initiate immediate notification of the alarm condition to the<br />

Dispatch Center.<br />

b. If a General Alarm Condition is annunciated the fire alarm system will<br />

immediately provide contact closure to the system.<br />

c. The system shall automatically broadcast emergency instructions whenever a<br />

General Alarm notification is transmitted. The System emergency message shall<br />

repeat for a minimum of 20 minutes or until the fire alarm system is manually<br />

reset.<br />

2. The system shall be provided with a sensing input which will accept a relay or contact<br />

closure from the fire alarm system which will completely <strong>and</strong> fully mute the system.<br />

3. When the relay or contact closure is removed, the system shall return to normal<br />

operational status with the settings that were active <strong>and</strong> in place just prior to the system's<br />

receipt of the contact closure.<br />