Guide Specification<br />

d. Axles: Minimum 1/2 inch diameter plated steel, hex-shaped, mechanically attached<br />

to blade.<br />

e. Mounting: Vertical.<br />

f. Electric Actuator: 24 V, 60 Hz, modulating, with position feedback.<br />

5. Digital Controller: Application specific controller. Programming logic <strong>and</strong> calibration in<br />

nonvolatile EPROM. Controller uses generic 0 - 10 vdc inputs <strong>and</strong> outputs for interface<br />

to building automation system.<br />

6. Air Straightener Section: 3 inches deep section contained in 5 inch long sleeve attached<br />

to damper-airflow monitor frame.<br />

7. Finish: Mill aluminum.<br />

D. Performance Data:<br />

2.9 CONTROLS<br />

1. Temperature Rating: Withst<strong>and</strong> -40 to 140<br />

degrees F.<br />

2. Accuracy: Plus or minus 5 percent.<br />

3. Leakage: Maximum of 2.0 cfm per square foot at<br />

1.0 inches wg pressure differential.<br />

4. Measures from 15 percent to 100 percent of unit<br />

nominal air flow.<br />

5. Adjusts air flow for temperature variations.<br />

6. Provides 2 to 10 volt DC signal corresponding to<br />

actual air flow.<br />

A. Coordinate with the Building Automation System for<br />

the Terminal.<br />

2.10 ELECTRICAL<br />

A. Motor:<br />

GUARANTEED MINIMUM FULL LOAD<br />

EFFICIENCY OF MOTORS<br />

Rated HP Nominal 1200 Nominal 1800<br />

RPM<br />

RPM<br />

1 82.5 85.5<br />

1.5 86.5 86.5<br />

2 87.5 86.5<br />

3 89.5 89.5<br />

5 89.5 89.5<br />

7.5 91.7 91.0<br />

10 91.7 91.7<br />

15 92.4 93.0<br />

20 92.4 93.0<br />

25 93.0 93.6<br />

30 93.6 94.1<br />

40 94.1 94.1<br />

50 94.1 94.5<br />

60 95.0 95.0<br />

75 95.0 95.0<br />

100 95.0 95.4<br />

125 95.4 95.4<br />

150 95.8 95.8<br />

200 95.4 95.8<br />

1. Enclosure Type: Totally enclosed, fan cooled.<br />

2. Inverter duty, NEMA Premium (TM) efficient motors as defined in NEMA MG 1.<br />

3. Motors must be “matched” with variable frequency drives.<br />

B. Electrical Requirements<br />

1. Where unit-mounted disconnects are provided, mount unit-mounted disconnect switches<br />

on exterior of unit.<br />

2. Variable Frequency Controllers shall be factory mounted in a ventilated compartment<br />

which is part of the air h<strong>and</strong>ling unit <strong>and</strong> factory wired to motors <strong>and</strong> controls. Access<br />

shall be through a louvered access door. The access door shall be flush with the outside<br />

of unit.<br />

CENTRAL-STATION AIR-HANDLING UNITS<br />

23 74 13 - 8 Mechanical Systems