Guide Specification<br />

part number, the description of the part, <strong>and</strong> the part number of the manufacturer’s<br />

product datasheet on which the information can be found.<br />

2. Provide manufacturer's ORIGINAL printed data sheets with the printed logo or<br />

trademark of the manufacturer for all equipment. Photocopied <strong>and</strong>/or illegible product<br />

data sheets shall not be acceptable.<br />

3. Indicated in the documentation will be the type, size, rating, style, <strong>and</strong> catalog number for<br />

all items proposed to meet the system performance detailed in this specification.<br />

4. CSFM listing sheet for each component<br />

5. Installer's NICET 3 Certification<br />

6. Letter or Certificate from the fire alarm manufacturer stating that the fire alarm contractor<br />

is an authorized EST Strategic Partner of the specified product.<br />

7. Submit a copy of the system supplier's training certification for the specified product<br />

issued by the manufacturer of the integrated life safety system.<br />

8. Equipment submittals <strong>and</strong> other documentation shall be incorporated bound with the<br />

above information indexed <strong>and</strong> tabbed for quick reference.<br />

C. Shop Drawings<br />

1. A complete set of shop drawings shall be supplied. The shop drawings shall be<br />

reproduced electronically in digital format. This package shall include but not be limited<br />

to:<br />

a. All drawings <strong>and</strong> diagrams shall include the contractor's title block, complete with<br />

drawing title, contractor's name, address, date including revisions, <strong>and</strong> preparer's<br />

<strong>and</strong> reviewer's initials<br />

b. Complete system bill of material with peripheral device backbox size information,<br />

part numbers, device mounting height information<br />

c. Detailed system operational description. Any Specification differences <strong>and</strong><br />

deviations shall be clearly noted <strong>and</strong> marked.<br />

d. A riser diagram that individually depicts all control panels, annunciators,<br />

addressable devices <strong>and</strong> notification appliances. Field addressable devices <strong>and</strong><br />

notification appliances may be grouped together by specific type per loop or circuit<br />

if allowed by AHJ.<br />

e. Complete 1/8" = 1'-0 scale floor plan drawing locating all system devices <strong>and</strong><br />

elevation of all equipment at the Fire Comm<strong>and</strong> Station. Floor plans shall indicate<br />

accurate locations for all control <strong>and</strong> peripheral devices as well as raceway size <strong>and</strong><br />

routing, junction boxes, <strong>and</strong> conductor size, <strong>and</strong> quantity in each raceway. All<br />

notification appliances shall be provided with a c<strong>and</strong>ela rating <strong>and</strong> circuit address<br />

that corresponds to that depicted on the Riser Diagram. If individual floors need to<br />

be segmented to accommodate the 1/8” scale requirements, KEY PLANS <strong>and</strong><br />

BREAK-LINES shall be provided on the plans in an orderly <strong>and</strong> professional<br />

manner. End-of-line resistors (<strong>and</strong> values) shall be depicted.<br />

f. All drawings shall be reviewed <strong>and</strong> signed off by an individual having a minimum<br />

of a NICET 3 certification in fire protection Engineering technology, subfield of fire<br />

alarm systems.<br />

g. Control panel wiring <strong>and</strong> interconnection schematics. The drawing(s) shall depict<br />

internal component placement <strong>and</strong> all internal <strong>and</strong> field termination points. Drawing<br />

shall provide a detail indicating where conduit penetrations shall be made, so as to<br />

avoid conflicts with internally mounted batteries. For each additional data-gathering<br />

FIRE DETECTION AND ALARM<br />

28 31 00 - 11 Fire Alarm