Guide Specification<br />

GUARANTEED MINIMUM FULL LOAD<br />

EFFICIENCY OF MOTORS<br />

Rated Nominal Nominal 1800<br />

HP 1200 RPM RPM<br />

1 82.5 85.5<br />

1.5 86.5 86.5<br />

2 87.5 86.5<br />

3 89.5 89.5<br />

5 89.5 89.5<br />

7.5 91.7 91.0<br />

10 91.7 91.7<br />

15 92.4 93.0<br />

20 92.4 93.0<br />

25 93.0 93.6<br />

30 93.6 94.1<br />

40 94.1 94.1<br />

50 94.1 94.5<br />

60 95.0 95.0<br />

75 95.0 95.0<br />

100 95.0 95.4<br />

125 95.4 95.4<br />

150 95.8 95.8<br />

200 95.4 95.8<br />

5. Motor Location: Mounted outside of cooling tower casing <strong>and</strong> cooling tower<br />

discharge airstream.<br />

6. Severe-duty rating with the following features:<br />

a. Rotor <strong>and</strong> stator protected with corrosion-inhibiting epoxy resin.<br />

b. Double-shielded, vacuum-degassed bearings lubricated with premium,<br />

moisture-resistant grease suitable for temperatures between minus 20 <strong>and</strong><br />

plus 300 deg F.<br />

c. Internal heater automatically energized when motor is de-energized.<br />

7. Motor Base: Adjustable, or other suitable provision for adjusting belt tension.<br />

P. Fan Discharge Stack: Material shall match casing, manufacturer's st<strong>and</strong>ard design.<br />

1. Stack Extension: Fabricated to extend above fan deck.<br />

2. Stack Termination: Wire-mesh, stainless-steel screens.<br />

Q. Gear-Drive, Oil-Level Switch: Low-oil-level warning switch for connection to a BMS.<br />

1. Switch shall, on reaching a low-oil-level set point recommended by cooling<br />

tower manufacturer, signal an alarm through the BMS.<br />

R. Controls: See Section "Building Automation System."<br />

S. Control Package: Factory installed <strong>and</strong> wired, <strong>and</strong> functionally tested at factory before<br />

shipment.<br />

1. NEMA 250, Type 4X enclosure with removable internally mount backplate.<br />

2. Control-circuit transformer with primary <strong>and</strong> secondary side fuses.<br />

3. Terminal blocks with numbered <strong>and</strong> color-coded wiring to match wiring<br />

COOLING TOWERS<br />

23 65 00 - 7 Mechanical Systems