12.02.2013 Views

Design and Construction Handbook - Los Angeles World Airports

Design and Construction Handbook - Los Angeles World Airports

Design and Construction Handbook - Los Angeles World Airports

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Guide Specification<br />

SECTION 26 28 26 - ENCLOSED TRANSFER SWITCHES<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. Section includes transfer switches in individual enclosures.<br />

1.2 REFERENCES<br />

A. National Electrical Manufacturers Association:<br />

1. NEMA ICS 10 - Industrial Control <strong>and</strong> Systems: AC Transfer Switch Equipment.<br />

B. International Electrical Testing Association:<br />

1. NETA ATS - Acceptance Testing Specifications for Electrical Power<br />

Distribution Equipment <strong>and</strong> Systems.<br />

C. Underwriters Laboratories Inc.:<br />

1.3 SUBMITTALS<br />

1. UL 1008 - Transfer Switch Equipment.<br />

A. Submit shop drawings after Short Circuit <strong>and</strong> Overcurrent Protective Device<br />

Coordination Study, is approved. Shop drawings submitted without approved study will<br />

be returned <strong>and</strong> not reviewed.<br />

B. AIC ratings shown on the single line diagrams are approximate values only. The AIC<br />

ratings of all submitted equipment must conform to the approved Short Circuit <strong>and</strong><br />

Overcurrent Protective Device Coordination Study.<br />

C. The electrical contractor shall submit 3@=1=0@ scale sketches of all electrical rooms <strong>and</strong><br />

areas including actual dimensions of all equipment in electrical rooms <strong>and</strong> indicate<br />

clearances per NEC, as well as door swings or other obstacles. Sketches shall be<br />

submitted along with or prior to shop drawing submittals. Shop drawing submittal<br />

without sketches shall be returned <strong>and</strong> not reviewed.<br />

D. Product Data: Submit catalog sheets showing voltage, switch size, ratings <strong>and</strong> size of<br />

switching <strong>and</strong> overcurrent protective devices, operating logic, control schematics, short<br />

circuit ratings, dimensions, <strong>and</strong> enclosure details.<br />

1.4 CLOSEOUT SUBMITTALS<br />

ENCLOSED TRANSFER SWITCHES<br />

26 28 26 - 1 Electrical Systems