Guide Specification<br />

2.3 PORTABLE OPERATOR'S TERMINAL<br />

A. Manufacturers:<br />

1. Dell Corporation.<br />

2. HP.<br />

3. Toshiba.<br />

B. Furnish device capable of accessing system data <strong>and</strong> capable of being connected to any point<br />

on system network or connected directly to any controller for programming, set-up, <strong>and</strong><br />

troubleshooting. Portable Operators Terminal uses Read (Initiate) <strong>and</strong> Write (Execute)<br />

Services as defined in Clauses 15.5 <strong>and</strong> 15.8, respectively, of ASHRAE St<strong>and</strong>ard 135, to<br />

communicate with BACnet objects in internetwork. Objects supported include: Analog input,<br />

analog output, analog value, binary input, binary output, binary value, device.<br />

C. Furnish IBM compatible lap-top style PC including software <strong>and</strong> hardware required with:<br />

1. Processor: Dual Core 2.1 GHz.<br />

2. Hard Drive: 500 Gigabyte (minimum).<br />

3. Memory: 4 Gigabyte DDR SDRAM.<br />

4. Drive 1: 24x CD/DVD Burner.<br />

5. WIFI Capable, with wireless card (internal), 802.11 b/g capable.<br />

6. Ports: Required serial, parallel, network communications, for USB ports, <strong>and</strong> cables for<br />

proper system operation.<br />

7. LAN Card: EtherNet - RJ45 (100 base-T minimum).<br />

8. Mouse: two-button optical type wireless.<br />

9. Keyboard: integral to PC.<br />

10. Screen: Minimum 15 inch display, color.<br />

11. Operating System: Windows 7.<br />

12. Battery: Minimum four hour service.<br />

2.4 CONTROL UNITS<br />

A. Units: Modular in design <strong>and</strong> consisting of processor board with programmable RAM<br />

memory, local operator access <strong>and</strong> display panel, <strong>and</strong> integral interface equipment.<br />

B. Battery Backup: For minimum of 100 hours for complete system including RAM without<br />

interruption, with automatic battery charger.<br />

C. Control Units Functions:<br />

1. Monitor or control each input/output point.<br />

2. Completely independent with hardware clock/calendar <strong>and</strong> software to maintain control<br />

independently.<br />

3. Acquire, process, <strong>and</strong> transfer information to operator station or other control units on<br />

network.<br />

4. Accept, process, <strong>and</strong> execute comm<strong>and</strong>s from other control unit's or devices or operator<br />

stations.<br />

5. Access both data base <strong>and</strong> control functions simultaneously.<br />

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC<br />

23 09 23 - 5 Mechanical Systems