Guide Specification<br />

2. Unless otherwise specified, all electric motors, provided under this Division shall be 60<br />

hertz. All motors shall be single phase or 3-phase as indicated on the Drawings. Motor<br />

starters shall be as scheduled on the Drawings or specified herein. If motors appliances or<br />

apparatus are furnished varying in horsepower <strong>and</strong>/or characteristics from those<br />

specified, accommodate the change at no additional cost to LAWA.<br />

B. Electrical.<br />

a. All fan <strong>and</strong> pump motors shall be of the premium efficiency type, NEMA <strong>Design</strong> A<br />

or B, continuous rated:<br />

GUARANTEED MINIMUM FULL LOAD EFFICIENCY<br />

Rated HP Nominal 1200 RPM Nominal 1800 RPM<br />

1 82.5 85.5<br />

1.5 86.5 86.5<br />

2 87.5 86.5<br />

3 89.5 89.5<br />

5 89.5 89.5<br />

7.5 91.7 91.0<br />

10 91.7 91.7<br />

15 92.4 93.0<br />

20 92.4 93.0<br />

25 93.0 93.6<br />

30 93.6 94.1<br />

40 94.1 94.1<br />

50 94.1 94.5<br />

60 95.0 95.0<br />

75 95.0 95.0<br />

100 95.0 95.4<br />

125 95.4 95.4<br />

150 95.8 95.8<br />

200 95.4 95.8<br />

1. Raceways. Furnish UL approved rigid conduit raceways, sized in accordance with the<br />

allowable fill permitted by the National Electric Code.<br />

2. Junction Boxes. Provide Appleton Electric Company, No. 4S-3/4 for interior use <strong>and</strong><br />

"FS" series with cast cover <strong>and</strong> neoprene gaskets for exterior use. Size junction boxes in<br />

accordance with the allowable fill permitted by the National Electric Code.<br />

3. Conductors. Furnish conductors conforming to UL, Fed. Specification. J-C-30, or IPCEA<br />

as applicable. Provide recently manufactured cable with guarantees <strong>and</strong> warranties<br />

initiated during the Contract period.<br />

C. Equipment Identification.<br />

1. Provide for each motor driven piece of equipment a "Dymo tape" identification tag, or<br />

3M Tape shall be l/2 inch (l3 mm) wide with color <strong>and</strong> location as directed.<br />

COMMON WORK RESULTS FOR HVAC<br />

23 05 00 - 5 Mechanical Systems