Guide Specification<br />

1. Calculate outside <strong>and</strong> return air enthalpy using measured temperature <strong>and</strong> relative<br />

humidity; determine energy expended <strong>and</strong> control outside <strong>and</strong> return air dampers.<br />

2. Operator comm<strong>and</strong>s:<br />

a. Add/delete fan status point.<br />

b. Add/delete outside air temperature point.<br />

c. Add/delete discharge controller point.<br />

d. Define discharge controller parameters.<br />

e. Add/delete return air temperature point.<br />

f. Add/delete outside air dewpoint/humidity point.<br />

g. Add/delete return air dewpoint/humidity point.<br />

h. Add/delete damper switch.<br />

i. Add/delete minimum outside air.<br />

j. Add/delete atmospheric pressure.<br />

k. Add/delete heating override switch.<br />

l. Add/delete evaporative cooling switch.<br />

m. Add/delete air flow rate.<br />

n. Define enthalpy deadb<strong>and</strong>.<br />

o. Lock/unlock program.<br />

p. Request control summary.<br />

q. Request HVAC point summary.<br />

3. Control summary:<br />

a. HVAC control system begin/end status.<br />

b. Enthalpy switchover optimal system status.<br />

c. Optimal return time system status.<br />

d. Current outside air enthalpy.<br />

e. Calculated mixed air enthalpy.<br />

f. Calculated cooling cool enthalpy using outside air.<br />

g. Calculated cooling cool enthalpy using mixed air.<br />

h. Calculated enthalpy difference.<br />

i. Enthalpy switchover deadb<strong>and</strong>.<br />

j. Status of damper mode switch.<br />

2.9 PROGRAMMING APPLICATION FEATURES<br />

A. Trend Point:<br />

1. Sample up to 248 points, real or computed, with each point capable of collecting 8<br />

samples at intervals specified in minutes, hours, days, or month.<br />

2. Output trend logs as line-graphs or bar graphs. Output graphic on terminal, with each<br />

point for line <strong>and</strong> bar graphs designated with a unique pattern or color, vertical scale<br />

either actual values or percent of range, <strong>and</strong> horizontal scale time base. Print trend logs<br />

up to 12 columns of one point/column.<br />

B. Alarm Messages:<br />

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC<br />

23 09 23 - 16 Mechanical Systems