A separate room shall be provided adjacent to WT control room to house the Dust suppression<br />

MCC, Pumps, compressors etc for the DS System by the Bidder. Bidder shall furnish the<br />

complete requirements quirements including size, cable trenches/opening, etc. The pressurized ventilation<br />

shall be provided by the Bidder in this Dust Suppression Room.<br />

The number of MCCs / DBs shall be provided as per requirement by the bidder.<br />

Following shall also be inclu included in the Bidder’s scope:<br />

• Pressurized ventilation system for the switchgearroom<br />

switchgearroom.<br />

• Pressurized ventilation system for the Dust Suppression cum MCC room.<br />

• Air conditioning of battery and battery charger rooms.<br />

• Exhaust fan in the transformer rooms.<br />

The bidder r shall supply the PLC for safe operation of WT System. Necessary integration with<br />

existing PLC of new coal yard will be scope of tender tenderer. . Design and installation of electrics shall<br />

ensure operation of complete integrated electrics of the various drives/m drives/mechanism without<br />

any constraint during maintenance.<br />

Bidder shall also consider sufficient numbers of local auxiliary PDBs to cater miscellaneous<br />

loads of WT System. These PDBs shall be located at various places and exact locations shall be<br />

finalized during g detailed engineering.<br />

HT Power cables and LT power/control cables shall be laid in different cable trays. LT power<br />

cables and LT control cables shall also be laid in different trays. 24V DC cables shall be laid<br />

entirely in different dedicated trays.<br />

Cable trays in single tier or in multitier shall be installed in vertical arrangement everywhere to<br />

avert coal accumulation and space reduction. Cable trays shall be supplied by the bidder.<br />

Power supply of all voltage levels including 415V AC or 220V DC, 24V DC etc, shall be arranged<br />

by Bidder himself by providing suitable systems. 24V DC supply shall be through screened<br />

cable to be supplied by the Bidder.<br />

Only at receiving point of 33KV, control supply of 415V AC and 220V DC shall be made<br />

available by the he purchaser purchaser.<br />

Following HT cabling shall also be included by the Bidder apart from the above:<br />

1. ACSR conductor for O/H transmission of 33kv line.<br />

2. Cabling required for underground track/road crossings of33 kV System including intake<br />

pump well feeder and ashpond feeder feeder.<br />

Standard power and control cables (Trailing Cables) of required sizes in adequate quantum<br />

shall be supplied and terminated by the Bidder. Hence, complete HT & LT trailing cables for<br />

Wagon Tippler, etc tc shall be supplied and laid by the bidder.<br />

Cables used for 24 VDC supply for PLC system shall be laid separately from 230 V AC control<br />

cables.<br />

Technical Specification:Sec-6, Electrical<br />

Page 6 of 97