The media of the filter shall be made from either special synthetic non non-woven bond fiber<br />

design or made from micro fiber glass media. It shall be supported with GI wire mesh or<br />

aluminum mesh and shall be housed in an aluminum sheet frame. It shall be of washable<br />

type several times.<br />

17.6.21 Package A/C Unit<br />

17.6.22 .22 A separate cubicle shall be provided within the overall casing to house the thermostatic<br />

controls, which shall be electric/electronic solid state, prewired and tested. The refrigerant<br />

system shall be protected by pressure limiting devices, electric and thermal overloads and<br />

unloading facilities to provide the required control range tolerances. A low voltage room<br />

thermostat shall be provided for wall mounting. The casing shall be fitted with all necessary<br />

coil drains and service connections/<br />

entries.<br />

17. . 6.23 PAC (duty/standby) units shall be selected manually and be ON/OFF switched. The units<br />

shall be fully packaged and incorporate integral room air sensing control thermostats and<br />

manufacturers work fitted safety interlocks. All controls shall be prewir prewired to unit mounted<br />

control/power terminal boxes.<br />

17.6.24 Ventilation and Air Conditioning system ducting<br />

17.6.25 All GI sheet metal ductwork required for ventilation and air conditioning system shall be<br />

furnished by the supplier. All ducts and plenums unless otherwise noted shall be constructed<br />

out of standard quality galvanised steel sheet. All sheet metal ducts shall be fabricated and<br />

installed in conformity to the requirements of IS:655. Steel supports for the ductwork shall<br />

be furnished as required. The thickness of ducting steel shall be 1 mm min. For ducting with<br />

large size exceeding 1300 mm it shall be 1.25 mm. The flexible connection between fan and<br />

ducting shall be on Teflon impregnated canvas. The zinc coating on GI sheet shall be 275<br />

gm/cm2.<br />

17.7 DATA SHEET : VENTILATION SYSTEM<br />

1.0 GENERAL<br />

1.1.0 Mech. Ventilation System: To provide ventilation using fans for specified areas.<br />

1.1.1 No. of air changes per hour<br />

(a) For overground building: Not less than 10 supply air changes & 7 Exhaust air<br />

changes<br />

(b) For underground areas: Not less than 15 supply air changes & 7 Exhaust air changes<br />

1.1.2 Equipment<br />

(1) Underground tunnel: Centrifugal fans/Axial Fans<br />

(2) All other places: Axial fans, roof ventilators<br />

1.2.0 Pressurised ventilati ventilation on system: To provide clean air to all MCC / Switchgear buildings<br />

1.2.1 No. of air changes per hour: Not less than 20<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />

Page 52 of 64