Capacity<br />

Nominal voltage (kV) 33<br />

Max system voltage (kV) 35<br />

Power frequency withstand voltage (kV) 75<br />

System earthing<br />

No. of phases<br />

Frequency<br />

Impulse test withstand voltage (kV) 170<br />

Short time current rating (for all current 25 kA for 3 sec<br />

carrying parts)<br />

Fault level (3 phase symmetrical) 25kA<br />

Type of Cooling<br />

Connection HV winding DELTA<br />

Connection LV winding STAR<br />

Connection Symbol<br />

HT/LT transformers shall be of the latest design, oil immersed type as per IS : 1886 and testing<br />

as per IS 2026 part I. . All dry type air natural transformers shall be suitable for indoor use line<br />

up with power control centre as unit type.<br />

Bidder shall ensure that manufacturer shall have his own in in-house house core cutting facilities on<br />

CNC machines.<br />

Special care shall be taken ken to make enclosed equipment proof against entry of rats, lizards and<br />

other creeping reptiles which may create electrical short short- circuits inside live equipment. The<br />

design of each transformer shall be such that the risk of accidental short short-circuits due to<br />

reptiles or vermin shall be obviated.<br />

The transformer shall be of cast resin type. The tap changing arrangement shall be of<br />

removable link type.<br />

Each transformer shall be suitable for operation at full rated power on all tappings without<br />

exceeding the temperature rise of 800C over the ambient of 50<br />

shall be F.<br />

o Each transformer shall be suitable for operation at full rated power on all tappings without<br />

C. Minimum class of Insulation<br />

The transformers shall be designed to be capable of withstanding, without injury, the thermal<br />

and mechanical effects of short short-circuits between phases or between n phase and earth at the<br />

terminals of any winding with full voltage applied across the other winding. All transformers<br />

shall be capable of withstanding specified through fault current for minimum of 2 seconds as<br />

per IS: 2026 (Part-1).<br />

The transformers shall all be designed to suppress harmonic currents, especially the third and<br />

fifth, so as to eliminate distortion in the wave form and consequent additional insulation<br />

Technical Specification:Sec-6, Electrical<br />

Low resistance earthed<br />

3<br />

50 Hz<br />

ONAN<br />

Dyn 11<br />

Page 32 of 97