and M. C. C. buildings shall be provided with suitable anodized aluminium grill. Fire - Proof<br />

doors with panic devices shall be provided at all fire exit points as pe per r the recommendations<br />

of statutory regulatory bodies These doors shall generally be as per IS : 3614 ( Part I and Part<br />

II ). Fire rating of the doors shall be as per requirements of statutory regulatory bodies.<br />

However minimum rating shall be 2 hours. Thes These e doors shall be double cover cover-plated types<br />

with mineral wool insulation. Hollow extruded section of minimum 3 mm wall thickness as<br />

manufactured by INDAL or equivalent shall be used for all aluminium doors, windows, and<br />

ventilators. Doors and windows on ext external ernal walls of the buildings having brick enclosures i.e.<br />

enclosure other than with Aluminium Industrial troughed sheet cladding, shall be provided<br />

with sunshade over the openings with width 600 mm more than the opening width.<br />

Projections from the wall fo for r the sunshade shall be 450 mm over window openings and 750<br />

mm over door openings. Minimum size of door provided should be 2.1 m high and 1.2 m<br />

wide, except for toiler rooms, where door may be 0.75 m wide. All doors ( other than those<br />

in W/C and urinal area a ) shall be double plate flush door shutters. For W/C and urinals area,<br />

wooden panel doors shall be provided. Area of windows shall be at least 10 % of the floor<br />

area of the respective building. The area of translucent polycarbonate sheet panels shall als also<br />

be at least 10 % of the floor area of the respective building. Monorail doors shall be provided<br />

with steel stays / chains etc for convenient operation of the shutters. The louvre blade shall<br />

be ‘Z’ shaped and made out of 18G sheets in EZ7 steel frames. TThe<br />

he frames shall be of ISMC<br />

100.<br />

24.2 Rolling Shutters<br />

Rolling Shutters/ grills shall be with motor drives, gear arrangement including all accessories<br />

and shall conform to IS: 6248. All electrical work shall be in strict accordance with the<br />

relevant Indian Electricity Rules. After installing the shutters, the Contractor shall test the<br />

performance of the shutter in presence of the Engineer. The shutters shall be smoothly<br />

operable under all ambient conditions. All control and locking devices shall give fault f ffree<br />

performance.<br />

25.0 PAINTING<br />

Painting of all steel structures, including seal plates, hand rails, steel doors & windows,<br />

ventilators, louvers, Rolling Shutters Stair Cases (except gratings), etc. shall be as per<br />

specification mentioned elsewhere in this document.<br />

26.0 Miscellaneous<br />

26.1 Ordinary form work shall be used in roofs and floor slabs in transfer houses, footings,<br />

pedestals, cable trenches, pits etc., Plywood form work shall be used for all over ground<br />

exposed work like columns, beams, floors an and d ceilings in control room and M. C. C. buildings.<br />

26.2 Monorail girders and fixtures shall be provided for monorails at the locations as<br />

required and as described elsewhere in these specifications or drawings. Monorail openings<br />

in the walls shall be prov provided ided with steel frame doors preferably sliding type or otherwise<br />

open able inside, access platforms and ladders.<br />

26.3Steel Steel frame around openings in roof and on external walls for mounting of exhaust<br />

fans shall be provided.<br />

26.4 Ready mix non - shrink nk cementitious grout of reputed manufacturer as approved by<br />

the Employer shall be used for grouting of block outs and foundation bolts, underpinning of<br />

base plates and machine bases. Crushing strength of grout shall be one grade higher than<br />

the foundation concrete. Minimum crushing strength shall be 30 N / mm2 unless higher<br />

strength requirement is specified by the equipment supplier or the grout manufacturers.<br />

26.5The The bottom of steel in case of cable / pipe galleries and trestles shall be generally 3m<br />