17.5.22 Condenser capacity control shall be provided by means of variable speed fans and ‘head<br />

pressure’ sensing.<br />

17.5.23 The evaporator air blower(s) shall be centrifugal forward curved type belt driven by<br />

individual motor(s) and suitable for the external static pressure. The fan assembly shall be<br />

isolated from the casing by anti anti-vibration vibration mounts. The fan/motor drive shall be capable of<br />

capacity adjustment by pulley changes within +15% of design duty.<br />

17.5.24 High efficiency filters shall be pprovided<br />

rovided in the main supply air duct and in the fresh air<br />

connection to return air duct.<br />

17.6 Construction Requirements<br />

17.6.1 General construction details of various equipment under Contractor’s scope shall be as<br />

elaborated in subsequent clauses below.<br />

17.6.2 Roof Ventilators and accessories<br />

Roof ventilators and accessories shall be provided as required.<br />

17.6.3 Impeller shall be axial flow type, cast in one piece finished all over and carefully dynamically<br />

balanced after final assembly. All impellers shall consist of high efficiency aerofoil blades.<br />

Impellers shall be mounted directly on the motor shaft.<br />

17.6.4 Casing shall be of heavy gauge construction and shall be properly reinforced for rigidity.<br />

Access door with suitable locking arrang arrangement shall be provided.<br />

17.6.5 Hood shall be of hinged type providing easy access to motor and impeller. It will also protect<br />

them from rain and any other contingencies. Weather Weather-proof proof lockable type disconnect switch<br />

shall be provided such that the hoods can be opened only when the disconnect switch is in<br />

‘OFF’ positions. On larger sizes of roof ventilators, hoods shall be of split construction. 15<br />

mm mesh galvanised bird screen shall be provided. The hoods will have low pressure drop<br />

across it.<br />

17.6.6 Suitable uitable arrangement shall be provided for mounting the roof ventilators such that ingress<br />

of rainwater into the building will be avoided completely.<br />

17.6.7 Axial Flow Fans<br />

Axial flow fans shall be provided as required.<br />

17.6.8 Impellers shall be axial fl flow ow type and single piece cast aluminum with aerofoil blades<br />

construction. It shall be finished all over and balanced dynamically. Impeller shall be<br />

mounted directly on the motor shaft.<br />

17.6.9 Casing shall be of heavy gauge construction properly reinforced for rigidity. It shall be<br />

provided with suitable supports. Access door shall be provided in the casing for easy access<br />

to motor and impeller. Suitable arrangement for mounting of motor shall be provided.<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />

Page 50 of 64