) Suitable access staircase with safety hand railing shall be provided to all floors of junction<br />

houses.<br />

s) Wall sheeting shall generally start from the lowest working floor and extend up to roof level<br />

with louvers at each h floor level to ensure adequate natural ventilation.<br />

t) Monorails for maintenance hoists shall be provided for maintenance and repair of various<br />

equipments located on the floors.<br />

18.2 Components of structures<br />

a) Gallery Trusses and Roof<br />

Gallery truss shall be of latticed type construction. The trusses shall be adequately braced at<br />

top and bottom chord level to transfer the horizontal wind forces to end portals.<br />

b) Stringer Beam<br />

These beams shall be suitably spaced to support the conveyor stringer supports and shall<br />

transfer load to gallery. Walkways on either side of the conveyor shall also be supported on<br />

these stringer beams.<br />

c) Supporting Trestles<br />

Intermediate trestles shall be two legged and shall deliver loads from gallery trusses to the<br />

foundations. In addition, four legged trestles shall be provided which will act as fixed support<br />

to transmit all longitudinal forces between expansion block, in addition to other forces.<br />

d) Junction Houses<br />

i) Floors - Floor beam layout shall be arranged to suit equipment llayout<br />

ayout as well as equipment<br />

anchoring system.<br />

ii) Columns - In addition to loads from floor and roof, columns shall be designed to transmit<br />

horizontal load due to belt tension/snapping of belts to the foundation.<br />

e) Belt Tensioning Device<br />

Suitable structures shall be provided to accommodate belt belt-tensioning tensioning device which may be<br />

located either under the conveyor gallery or in the junction house itself.<br />

f) Wall Structures<br />

(i) Wall runners with necessary sag rods shall be provided to support wall sheeting in<br />

conveyor galleries and junction houses.<br />

(ii) Walls shall be provided with louvers and translucent sheeting at appropriate levels,<br />

to provide natural ventilation and lighting.<br />

g) Access stairs, walkways, platforms, ladders, hand railing etc.<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />